65
TECHNICAL SPECIFICATIONS:
________________________________________________________________________________________
10.
TECHNICAL SPECIFICATIONS:
Supply
Voltage
Line
to
Line
208-600V
(to
be specified) + 10%-15% for all models
Frequency
45
±
65 Hz (Fixed or variable frequency source)
Control Supply
115V or 230V (to be specified) +10% - 15%
Load
Three
phases,
three
wires,
squirrel
cage
induction
motor.
Start-Stop Parameters:
Starter FLC
6WDUWHU¶V)XOO/RDG&XUUHQWDFFRUGLQJWR6HOHFWRU*XLGH
Motor FLA
Motor Full Load Ampere 50-100% of Starter FLC (Full Load Current).
Pump and Torque Control Curves
Field selectable curves preventing Over-pressure during start and Water
Hammer during stop.
Pulse Start Duration
A pulse of 80% Un, adjustable range 0.1-1 Sec, for starting high friction loads.
Initial
Voltage,
5-80%
Un
Initial Current
100-400% of Motor FLA
Current
Limit
100-500%
of
Motor
FLA
Acceleration
Time
1-90
Sec
Deceleration
Time
1-90
Sec
Motor Protection:
Too
Many
Starts Maximum
number
of starts, range: Off or 1-10, during a time period 1-60 min.
Starts inhibit
Period of 1-60 min, during which starting is prevented, after Too Many Start
fault.
Long Start Time (Stall protection)
Maximum allowable starting time 1-30 sec. (1-250sec. in WIDER SETTINGS)
Over Current (Shear-pin)
Two operation functions: during starting trips the starter at 850% and during
running at 100-850% In, both within 1 Cycle (after internal delay).
Electronic Overload (I
2
t)
Adjustable IEC and MEMA curves.
Under Current
Trips when current drops below 20-90% In, time delay 1-40 sec.
Under Voltage*
Trips when main voltage drops below 50-90%, time delay 1-10 Sec
Over Voltage
Trips when main voltage increase above 110-125%, time delay 1-10 sec.
Phase Loss, Under/Over Frequency
*
Trips when one or two phases are missing and frequency is 45Hz. or 65Hz.
Phase Sequence
Trips when phase sequence is wrong
Shorted SCR or Wrong connection
Prevents starting, trips if motor is not connected / incorrectly connected to the
starter, or in case one or more SCRs have been shorted
Heat Sink Over temp
Trips when heat-
VLQNWHPSHUDWXUHULVHVDERYHÛ&
External fault
Trips when an External Contact closes for 2 sec.
*
With optional Auto Reset.
Control:
Displays LCD
in
4
±
Field selectable languages and 4 LEDs.
Keypad
6 keys for easy setting
Fault Contact
2 Contacts, 8A, 250VAC, 2000VA
Aux. Contact
±
Imm. or End Of Acc.
2 Contacts, 8A, 250VAC, 2000VA
Temperatures:
Operating
-
ÛWRÛ&
Storage -
ÛWRÛ&
Standards:
Dielectric
Test
2500VAC
Degree of Protection
IP 20 for frame size D1, IP 00 for frame sizes D2-D5
EMC
Emissions
EN 55011
CISPR 11 Class A
Immunity
EN
55082-2
ESD 8KV air, IEC 801-2
Electric
RF
field
10
V/m,
20-1000MHz,
IEC
801-3
Fast
transients
2KV,
IEC
801-4
Safety
EN
600947-1
Related to safety requirements.
Designed
and
assembled to conform with UL508C