WARNING!
Fatal electric shock hazard!
Cables conducting mains voltage must be covered by the contact protection
inside the inverter.
■
■
Always route the connecting cable through the middle cable gland
(Figure 5/Pos. 2).
2. Connect the wires as follows:
– Wire stripping length: 7 mm
Contact
Description
K6
Control line
N
Neutral conductor
3. Close the unused holes in the cable gland using the locking pins.
4. Tighten the cable gland (wrench size: 34 mm).
5. Check the cable strain relief.
6. Close the inverter by
– inserting the contact protection;
– then tighten the cover.
You can now switch the inverter on as described in the instruction manual.
4�4�4 Multi-function relay
The multi-function relay can be used as status signaling contact for the remote control of
the inverter or for the control of self-consumption (see section 4.4.7). The configuration
as status signaling contact is either done using the inverter's graphics display (see section
5.1) or with MaxTalk 2.
11
12
14
NC
Figure 7 Contact scheme of multi-function relay
Connection conditions
■
■
Connectable cable diameter: min. 9.5 mm / max. 12.5 mm
■
■
Connectable conductor cross-sections: min. 0.25 mm
2
/ max. 2.5 mm
2
■
■
Max. switching voltage: 250 V
AC
/ 30 V
DC
■
■
Max. switching current: 1.5 A (no internal fuse present)