WARNING!
Fatal electric shock hazard!

Cables conducting mains voltage must be covered by the contact protection 
inside the inverter.

Always route the connecting cable through the middle cable gland 
(Figure 5/Pos. 2).

2.  Connect the wires as follows:

 

– Wire stripping length: 7 mm

Contact

Description

K6

Control line

N

Neutral conductor

3.  Close the unused holes in the cable gland using the locking pins.
4.  Tighten the cable gland (wrench size: 34 mm).
5.  Check the cable strain relief.
6.  Close the inverter by

 

– inserting the contact protection;

 

– then tighten the cover.

You can now switch the inverter on as described in the instruction manual.

4�4�4  Multi-function relay

The multi-function relay can be used as status signaling contact for the remote control of 
the inverter or for the control of self-consumption (see section 4.4.7). The configuration 
as status signaling contact is either done using the inverter's graphics display (see section 
5.1) or with MaxTalk 2.

11

12

14

NC

Figure 7  Contact scheme of multi-function relay

Connection conditions

Connectable cable diameter: min. 9.5 mm / max. 12.5 mm

Connectable conductor cross-sections: min. 0.25 mm

2

 / max. 2.5 mm

2

Max. switching voltage: 250 V

AC

 / 30 V

DC

Max. switching current: 1.5 A (no internal fuse present)

Содержание 10 005 380

Страница 1: ...Installation manual SolarMax P series I O module...

Страница 2: ...Sputnik Engineering AG L nggasse 85 CH 2504 Biel Bienne Email info solarmax com Sputnik Engineering AG 2014...

Страница 3: ...4 4 3 SPI logic 14 4 4 4 Multi function relay 15 4 4 5 Lightning protection monitor 16 4 4 6 S0 interface 17 4 4 7 Control of self consumption 18 5 Configuration 22 5 1 Configuring the status signalin...

Страница 4: ...ns at all times If this original document is lost an up to date version of this instal lation manual can be downloaded from our website at any time www solarmax com 1 4 Symbols used The following safe...

Страница 5: ...the inverter while it is in operation Before you start installation work ensure that all connectors and cables are de energized Remove the cover and the contact protection on the inverter as describe...

Страница 6: ...ntrol of the PV power plant It is inserted into the slot provided in the inverter 3 1 Identification The I O module can be identified by a sticker on the printed circuit board see Figure 1 Pos 1 1 Fig...

Страница 7: ...nterface control of self consumption S0 BS Lightning protection monitor BS N External shutdown external power control SPI frequency monitoring NA External shutdown NC not used 11 Multi function relay...

Страница 8: ...s and possible damage In the case of an inadequate delivery please contact your dealer or the SolarMax Service Center Installationsanleitung SolarMax P Serie I O Modul 2 3 4 5 1 Figure 3 Content of de...

Страница 9: ...erter as described in the instruction manual Observe the safety instructions in the inverter instruction manual ATTENTION Damage due to electrostatic discharge Avoid electrostatic discharge ESD when h...

Страница 10: ...I O module 6 Connect the wiring to the interfaces as described in Section 4 4 7 Complete the installation of the I O module by inserting the contact protection such that you hear the snap closures eng...

Страница 11: ...gure 5 Wiring of connections in the inverter No Description 1 Left cable gland For lightning protection monitor S0 interface energy counter 2 Middle cable gland For external shutdown external power co...

Страница 12: ...conductor cross sections min 0 25 mm2 max 2 5 mm2 Max input current 25 mA Max input voltage 230 VAC Procedure 1 Open the inverter as described in the instruction manual WARNING Fatal electric shock ha...

Страница 13: ...interface 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 a b c a b c a b c a b c a b c a b c K6 K5 K4 K3 K2 K1 L 230 V I max 150 mA N I 25 mA N K5 K6 K4 K3 K2 K1 NA Ripple control receiver Inverte...

Страница 14: ...l if the SPI logic is used at the same time N Neutral conductor 3 Close the unused holes in the cable gland using the locking pins 4 Tighten the cable gland wrench size 34 mm 5 Check the cable strain...

Страница 15: ...ct protection then tighten the cover You can now switch the inverter on as described in the instruction manual 4 4 4 Multi function relay The multi function relay can be used as status signaling conta...

Страница 16: ...d wrench size 34 mm 5 Check the cable strain relief 6 Close the inverter by engaging the contact protection then tighten the cover You can now switch the inverter on as described in the instruction ma...

Страница 17: ...ce In accordance with DIN EN 62053 31 this interface only available for the I O module item no 10005981 can be used to connect an energy counter to the inverter for the purpose of the control self con...

Страница 18: ...he control of self consumption Connection is via the inter faces of the I O module Several different operating modes can be selected Operating mode Description Grid feed in limitation As the inverter...

Страница 19: ...feed in limitation is configured using the free MaxTalk 2 Pro service software S0 S0 BS BS 12 NC 14 11 kWh R kWh N Inv PV C 0 20 40 60 80 100 120 Figure 8 Wiring in Grid feed in limitation operating m...

Страница 20: ...rter s graphics display or using MaxTalk2 The S0 interface energy counter is configured with MaxTalk 2 Pro S0 S0 BS BS 12 NC 14 11 R K N Inv PV kWh kWh C 0 20 40 60 80 100 120 Figure 9 Wiring in Pac e...

Страница 21: ...de is configured on the inverter s graphics display or using MaxTalk 2 S0 S0 BS BS 12 NC 14 11 R K N Inv PV kWh kWh C 0 20 40 60 80 100 120 Figure 10 Wiring in Pac inverter operating mode Legend R con...

Страница 22: ...module submenu 2 In MF relay select the Status relay setting 3 Select the required setting under Mode Setting Description Off The status signaling contact is always open Grid If the inverter starts ma...

Страница 23: ...e software 5 2 1 Graphics display configuration Procedure 1 In the Settings menu select the SPD Monitor parameter 2 Select the required setting Setting Description Off The lightning protection monitor...

Страница 24: ...on relay on off Energy meter Pac W Start time End time Enable threshold Figure 11 Pac electric meter operating mode The time window of the control of self consumption is defined by the Start time and...

Страница 25: ...1 Start MaxTalk 2 2 Connect MaxTalk 2 to the inverter 3 Select the inverter in the plant tree 4 In the Device menu click Settings The Settings tab will be opened 5 In the Mode menu Multi function rela...

Страница 26: ...cedure 1 Go to the Settings menu and select the I O module submenu 2 In MF relay select the Self consumption setting 3 In Mode select the Pac inverter operating mode 4 Configure the parameters Paramet...

Страница 27: ...he safety instructions in the inverter instruction manual Procedure 1 Open the inverter as described in the instruction manual 2 Use a voltage tester to check that all connections at the inverter and...

Страница 28: ...replaced by SPUTNIK service personnel within a reasonable time in either case free of charge unless this is impossible or disproportionate SPUTNIK may decide at its own discretion whether a device wil...

Страница 29: ...mentioned in the paragraph above 4 Warranty Period in Case of Repair Replacement In case of repair or replacement of devices under this warranty the repaired respectively replaced device will inherit...

Страница 30: ...device by SPUTNIK Central Inverters The extension of the basic warranty can be ordered within 3 months after pur chase but the latest within 12 months after dispatch by SPUTNIK b Extent Full warranty...

Страница 31: ...en 31 Notes...

Страница 32: ...SolarMax Service Center hotline solarmax com www solarmax com service 2014 07 en...

Отзывы: