5 Configuration
The I/O module will be detected automatically by the inverter. The I/O module inputs can
be configured individually. The following functions can only be configured with the free
MaxTalk 2 Pro service software:
■
■
External shutdown
■
■
External power control
■
■
SPI logic
■
■
Grid feed-in limitation
■
■
S0 interface (energy counter)
The required "SolarMax P series parameter configuration using MaxTalk 2 Pro" operating
manual can be downloaded from our website (www.solarmax.com "Downloads" area).
5�1
Configuring the status signaling contact
The status signaling contact for the remote monitoring of the inverter offers four setting
options. These can be configured on the graphics display of the inverter or with MaxTalk 2.
5�1�1 Graphics display configuration
Procedure
1. Go to the "Settings" menu and select the "I/O module" submenu.
2. In "MF relay" select the "Status relay" setting.
3. Select the required setting under "Mode":
Setting
Description
Off
The status signaling contact is always open.
Grid
If the inverter starts mains operation, the status signaling contact is
closed immediately and remains closed as long as the inverter feeds
into the grid. If the inverter does not feed into the grid, the status
signaling contact is opened after expiry of the adjustable delay.
Error
When a warning, a failure, or a device error occurs on the inverter
(for error messages see the instruction manual), the status signaling
contact is closed after expiry of the adjustable delay. The status
signaling contact is immediately opened when the fault is no longer
present (factory setting).
On
When the inverter is switched on (sufficiently high DC input voltage),
the status signaling contact closes. The status signaling contact will
not re-open unless the inverter is switched off (DC input voltage too
low).
4. Select "Delay".
5. Adjust the required delay time: