4�4�7�1 Grid feed-in limitation
For the connection diagram in "Grid feed-in limitation" mode see Figure 8: the energy
counter that measures the power fed in at the grid connection point is connected to the
S0 interface of the I/O module.
The grid feed-in limitation is configured using the free MaxTalk 2 Pro service software.
S0−
S0+
BS−
BS+
12
NC
14
11
kWh
R
kWh
N
Inv
PV
°C
0
20
40
60
80
100
120
Figure 8 Wiring in "Grid feed-in limitation" operating mode
Legend:
R: consumer / Inv: inverter / PV: PV generator / N: grid connection point / kWh:
energy counter
Procedure
■
■
Connect the energy counter as described in section 4.4.6.
■
■
Use MaxTalk 2 Pro to configure the max. feed-in power and the S0 interface (energy
counter).