en
23
Parameter
Description
Value range
Unit
Delay
Delay time of status relay
0…99
min
5�1�2 Configuration with MaxTalk 2
Procedure
1. Start MaxTalk 2
2. Connect MaxTalk 2 to the inverter.
3. Select the inverter in the plant tree.
4. In the "Device" menu, click "Settings". The "Settings" tab will be opened.
5. In the "Status relay function" menu select the setting of your choice.
– For a description of settings see section 5.1.1.
5�2
Configuring the lightning protection monitor
The lightning protection monitor can be configured on the graphics display of the inverter
or with the free MaxTalk 2 service software.
5�2�1 Graphics display configuration
Procedure
1. In the "Settings" menu, select the "SPD Monitor" parameter.
2. Select the required setting:
Setting
Description
Off
The lightning protection monitoring is deactivated.
Warning
When the lightning protection operates, the warning "Failure, light-
ning protection" is displayed (on the graphics display and in MaxTalk).
The inverter will continue to feed into the mains. The status signaling
contact will be closed (factory setting).
Error
When the lightning protection operates, the status message "SPD
failure" is displayed (on the graphics display and in MaxTalk). The
inverter will disconnect from the mains. The status signaling contact
will be closed.
5�2�2 Configuration with MaxTalk 2
Procedure
1. Start MaxTalk 2
2. Connect MaxTalk 2 to the inverter.