16
■
■
Max. cable length: 50 m
Procedure
1. Open the inverter as described in the instruction manual.
WARNING!
Fatal electric shock hazard!
Cables conducting mains voltage must be covered by the contact protection
inside the inverter.
■
■
Always route the connecting cable through the middle cable gland
(Figure 5/Pos. 2).
2. Connect the wires as follows:
– Wire stripping length: 7 mm
Contact
Description
11
COM
12
Opener (when used as status signaling contact: opener in the case of error)
14
Closer (when used as status signaling contact: closer in the case of error)
NC
not used
3. Close the unused holes in the cable gland using the locking pins.
4. Tighten the middle cable gland (wrench size: 34 mm).
5. Check the cable strain relief.
6. Close the inverter by
– engaging the contact protection;
– then tighten the cover.
You can now switch the inverter on as described in the instruction manual.
4�4�5 Lightning protection monitor
This interface can be used for monitoring an external lightning protection module. The
configuration is done using the inverter's graphics display (see section 5.2.1) or with
MaxTalk 2.
When the remote signaling contact of the lighting protection module connected to the
input closes, the inverter displays the corresponding status message/warning on the
graphics display. It is possible to connect multiple lightning protection modules in parallel
to the lightning protection input.
Connection conditions
■
■
Connectable cable diameter: min. 9.5 mm / max. 12.5 mm
■
■
Connectable conductor cross-sections: min. 0.25 mm
2
/ max. 2.5 mm
2