3. Connect the wires as follows:
– Wire stripping length: 7 mm
– Ensure the polarity is right.
Contact
Description
S0+
Pulse input (plus pole)
S0–
COM (minus pole)
4. Close the unused holes in the cable gland using the locking pins.
5. Tighten the cable gland (wrench size: 34 mm).
6. Check the cable strain relief.
7. Close the inverter by fitting and tightening the cover.
You can now switch the inverter on as described in the instruction manual.
4�4�7 Control of self-consumption
The inverter has functions for the control of self-consumption. Connection is via the inter-
faces of the I/O module. Several different operating modes can be selected.
Operating mode
Description
Grid feed-in limitation
As the inverter controls self-consumption it keeps within a max-
imum feed-in power at the grid connection point. This operating
mode is available only for the I/O module, item no. 10 005 981.
Pac electric meter
The inverter controls the consumer loads in accordance with the
power fed into the grid. The power output is measured with an
energy counter. This operating mode is available only for the I/O
module, item no. 10 005 981.
Pac inverter
The inverter controls the consumer loads in accordance with its
output power.