SYSTEM SETUP AND OPERATION GUIDE FOR THE SOLAR STIK USAF G-BOSS MEDIUM AND HEAVY HYBRID POWER SYSTEM
PRELIMINARY DRAFT
Full Charge
This status indicates that the PRO-Verter is in Battery Saver mode. This mode maintains the
batteries without overcharging. After four (4) hours of float charging, the charger turns off and “Full
Charge” displays (charger is now in Battery Saver mode). If the battery voltage drops to ≤ 25.2, the
charger automatically initiates another four (4) hours of float charging. This cycle helps to ensure the
batteries are maintained and continues as long as AC power is continuously connected to the AC
input. “Full Charge” only displays if Multi-Stage is selected from the SETUP: 03G Final Charge Stage
menu.
Silent
This displays at the end of the Absorption stage if Silent is selected from the SETUP: 03G Final
Charge Stage menu. In Silent mode, the charger is not actively charging but does monitor the
battery voltage. When the battery voltage reaches the Set Rebulk Voltage setting (from 03G Final
Charge Stage menu), the charger will restart a Bulk and Absorb charge cycle and then transition
back into Silent mode at the end of the Absorb cycle.
Back to
Quick
Links page
Secondary Scrolling Status Messages
These displays alternate with the inverter/charger status to indicate other pertinent messages.
Gen Warm-up
The AGS unit has commanded the generator to run, but the PRO-Verter will not connect to the
generator’s AC output until the generator warm-up time is complete.
Gen Cool Down
The autostop setting (FAVS F5: Gen Run VDC > Set Stop Gen V= 28.0) has been met and the
generator has been disconnected from the PRO-Verter. However, the generator still runs until the
FAVS F5: Gen Run VDC > Set Stop Gen = 30 Minutes and cooldown (Setup: 04J) time is met.
Note:
Most faults (inverter, AGS, and BMK) also alternate with the inverter/charger status.