December 2020
|
Solar Stik
®
, Inc.
72
|
SYSTEM SETUP AND OPERATION GUIDE FOR THE SOLAR STIK USAF G-BOSS MEDIUM AND HEAVY HYBRID POWER SYSTEM
PRELIMINARY DRAFT
Total AH Out
This meter displays the total amp hours removed from the battery since the PRO-Verter was first
connected. This display can be used as a battery service life indicator. The value is displayed in 0.1 k
[or 100 amp hours (“k” equals 1000)] resolution up to a maximum of 6553.5 k amp hours (6,553,500
amp hours). The displayed number resets to 0.0 k when the PRO-Verter is disconnected from power.
Minimum VDC
This menu displays the lowest battery voltage since the last reset. The voltage shown on the display
is averaged each second, and is helpful when troubleshooting or detecting an overdischarge
condition.
To reset this display
, press and hold the SELECT dial for three (3) seconds while the
Minimum VDC display is shown. After this value has been reset, the display will begin monitoring
and showing new minimum DC input values. If the battery monitor is not connected or not
communicating, the display will show “0.0”.
Maximum VDC
This menu displays the highest battery voltage since the last reset. The voltage shown on the display
is averaged each second, and this allows a check of the charging system (battery charger, charge
controller, etc.) to ensure the charging voltage has been attained. This display is also helpful when
troubleshooting or detecting if an overcharge condition has occurred.
To reset this display
, press
and hold the SELECT dial for three (3) seconds while the Maximum VDC display is shown. After this
value has been reset, the display begins monitoring and showing new maximum DC input values. If
the battery monitor is not connected or not communicating, the display shows “0.0”.
Days Since 100% SOC
This read-only menu displays the number of days since the battery was at 100% SOC.