77
December 2020
|
Solar Stik
®
, Inc.
SYSTEM SETUP AND OPERATION GUIDE FOR THE SOLAR STIK USAF G-BOSS MEDIUM AND HEAVY HYBRID POWER SYSTEM
PRELIMINARY DRAFT
04K Gen 100% SOC
Set
Gen 100% SOC
Start Days = 3
Set 100% SOC Run
Hour = 8:00A
Set 100% SOC Run
Minute = 0:00A
Set 100% SOC Run
AM-PM = 0:00 P/A
Set
Gen 100% SOC
Days = 1-255 Days
Set 100% SOC Run
Hour = 00:00A
Set 100% SOC Run
Minute = 0:00A
Set 100% SOC Run
AM-PM = 0:00A
Default Off
Range: Off, 1-255
1. Press the SETUP Button on the PRO-Verter user
interface (password may be required).
2. Navigate to 04K Gen 100% SOC. Press SELECT to enter
this menu.
3. Enter and save the values best suited for your
application into each of the fields. Start with the
frequency (e.g., every 3 days) as shown and at an
appropriate time of day.
4. Confirm that the SOC of the System battery bank
reported in METER 05B is 100%. .
Notes
• Ensure that the System clock is set to local time.
• Turn OFF Max Gen Run Time (SETUP 04F) to avoid generator shutdown before 100% SOC is
achieved.
• The
Gen 100% SOC Start Days
setting uses information from the BMK’s
METER 05J Days Since
100% SOC
to determine how many days have passed since the battery bank has not been
charged to 100% SOC.
• A valid SOC number must display in
METER 05B Battery SOC
for the BMK’s
METER 05J Days
Since 100% SOC
menu to accumulate and display days (Think’n, No Comm, Internal Fault,
Power-up Fault, or Unknown Fault ## are not valid SOC numbers).
• Once the BMK’s
METER: 05B Battery SOC
displays 100%, the AGS stops the generator and the
BMK’s
METER: 05J Days Since 100% SOC
display resets to “0 days”.
• If the generator does not start at the scheduled time (i.e., AGS fault, generator runs out of fuel,
etc.,), one more day must pass before another attempt is made to charge to 100% SOC.
System Recovery to Restore Overdischarged Batteries
1. Disconnect/turn off all AC loads (if present) connected to the PRO-Verter.
2. Turn off the power switch on all but one (1) of the batteries or disconnect all but one (1) battery
from the Inter-Connect circuit if the battery does not have a power switch.
3. Connect a 120 VAC power source to the PRO-Verter AC Input port. Turn on PRO-Verter Main
Power switch.
4. Push the FAVs F1 button. Press SELECT. Reduce max charge rate to 10%. Press SELECT.
Press HOME button.
5. Toggle and HOLD the System Recovery momentary switch until the battery/bus voltage rises
to operational level and the PRO-Verter CHG LED is constant green. This may take several
minutes.
6. Once the PRO-Verter enters charging mode and the current is flowing, turn on or reconnect all
batteries.
7. Allow the PRO-Verter to charge at 10% rate until all ESM voltages have returned to operational
levels.
8. Return max charge rate to 100%.
9. Charge all batteries fully.
10. Reconnect and/or turn on PRO-Verter loads.
Note:
The recovery feature works even if the inverter has been turned off in the program settings.