PSS-G/RAID Alternative Energy System Deployment Guide
SETUP Button Menus (continued)
Setup: 04 AGS Setup
Set Gen Run Temp
Off
Set Gen Run Temp
Time = 1.0 Hrs
04E Gen Run Temp
SETUP
Status
04 AGS Setup
Set Gen Run Temp
Start=Ext. Input
Press to turn
“On”
Press SELECT;
scroll to appropriate
time.
Scroll to “On”;
press SELECT.
Default setting.
If not set,
choose 1.0 Hrs
(option may not
be available).
If the PRO-Verter 7000 goes into
Overtemp
or TmfrOvertemp
Fault mode during peak
demand, ensure that the AGS is set to Auto
(CTRL 03) and that Set Gen Run Temp is
set to “1.0 Hrs” (if this option is available) by
following the Menu Map below:
04H Gen Exercise
Off/On
Set Gen Run Temp
Start = OFF
Set Gen Run Temp
Time =0.5
continued
SETUP
04E Gen Run Temp
Ext Input
Status
04 AGS Setup
Set Gen Run Temp
Start = Ext Input
Set Gen Run Temp
Time =0.5-25.5 Hrs
Default = OFF
Set Gen Run Temp
Start = 65F-95F
Set
Max Gen Run
Time = 12.0 Hrs
04F Max Gen Run
Time = OFF
Set
Max Gen Run
Time = 0.1-25.5 Hrs
Default = 12.0 Hrs;
Range: 0.1-25.5 Hrs
Set
Quiet Time
OFF
Set Start Quiet
Hour = 1:00
Set Start Quiet
Minute = 00:45P
Set Start Quiet
AM-PM = 0:00P
04G Quiet Time
Press Select
Set
Quiet Time
ON
Set Start Quiet
Hour =1:00-12:00PM
Set Start Quiet
Minute = 0:00P
Set Start Quiet
AM-PM = 0:00A
Default = OFF
Set Stop Quiet
Hour = 1:00P
Set Stop Quiet
Minute = 00:45P
Set Stop Quiet
AM-PM = 00:00P
Set Stop Quiet
Hour= 12:00P
Set Stop Quiet
Minute = 00:00A
Set Stop Quiet
AM-PM = 00:00A
Set Quiet Time
Topoff = 30-120Min
Set Quiet Time
Topoff = Off
Set
Gen Exercise
Days=2
Set Exercise Run
Hour=8:00
Set Exercise Run
Minute=#:00-#:59
Set Exercise Run
AM-PM= 8:00P
Set
Gen Exercise
Days=1-255 Days
Set Exercise Run
Hour=1:00-12:00A
Set Exercise Run
Minute= 8:00
Set Exercise Run
AM-PM= 8:00A
Set Exercise Run
Time= 1-25.5 Hrs
Set Exercise Run
Time= 2.0 Hrs
04I Gen Warm-up
Time = 15 Sec
Gen Warm-up
Time = 15 Sec
Gen Warm-up
Time =0-127 Sec/Min
Default = 60 Seconds
OFF = 0 Seconds
Range: 0-127 seconds; 0-127 minutes
04J Gen Cool Down
Time =
60 Sec
Gen Cool Down
Time = 60 Sec
Gen Cool Down
Time =0-127 Sec/Min
Default = 60 Seconds
OFF = 0 Seconds
Range: 0-127 seconds; 0-127 minutes