ANNUAL PERFORMANCE CALCULATIONS FOR EUROPE
42
L SYSTEMS
Annual performance calculations of Solahart thermosiphon L systems with the L collector according to EN12976
SolarKeyMark Systems ITW Test Report 11SYS92-01 for the 151L (150 tank, 1 collector), 181L (180 tank, 1 collector),
and 302L (300 tank, 2 collectors) systems.
Qd = energy demand
QL = solar energy (load)
f-sol = solar fraction
Model
151L
151L
151L
151L
Demand
110 litres / day
140 litres / day
170 litres / day
200 litres / day
Location
Qd
MJ/a
QL
MJ/a
f-sol
%
Qd
MJ/a
QL
MJ/a
f-sol
%
Qd
MJ/a
QL
MJ/a
f-sol
%
Qd
MJ/a
QL
MJ/a
f-sol
%
Stockholm
59.6°N
6107
2712
44.5
7772
3031
39.0
9438
3048
32.3
11103
3053
27.5
Wurzburg
49.5°N
5854
2816
48.1
7450
3174
42.6
9047
3248
35.9
10643
3246
30.5
Davos
46.8°N
6628
3930
59.3
8435
4319
51.2
10243
4333
42.3
12050
4338
36.0
Athens
38.0°N
4545
3504
77.1
5784
4095
70.8
7024
4418
62.9
8263
4594
55.6
Model
181L
181L
181L
181L
Demand
140 litres / day
170 litres / day
200 litres / day
250 litres / day
Location
Qd
MJ/a
QL
MJ/a
f-sol
%
Qd
MJ/a
QL
MJ/a
f-sol
%
Qd
MJ/a
QL
MJ/a
f-sol
%
Qd
MJ/a
QL
MJ/a
f-sol
%
Stockholm
59.6°N
7772
3334
42.9
9438
3671
38.9
11103
3697
33.3
13879
3706
26.7
Wurzburg
49.5°N
7450
3457
46.4
9047
3863
42.7
10643
3927
36.9
13304
3938
29.6
Davos
46.8°N
8435
4791
56.8
10243
5234
51.1
12050
5242
43.5
15063
5257
34.9
Athens
38.0°N
5784
4361
75.4
7024
4973
70.8
8263
5313
64.3
10329
5609
54.3
Model
302L
302L
302L
302L
Demand
200 litres / day
250 litres / day
300 litres / day
400 litres / day
Location
Qd
MJ/a
QL
MJ/a
f-sol
%
Qd
MJ/a
QL
MJ/a
f-sol
%
Qd
MJ/a
QL
MJ/a
f-sol
%
Qd
MJ/a
QL
MJ/a
f-sol
%
Stockholm
59.6°N 11103
5230
47.1
13879
5871
42.3
16655
6146
36.9
22206
6195
27.9
Wurzburg
49.5°N 10643
5375
50.5
13304
6093
45.8
15965
6498
40.7
21286
6577
30.9
Davos
46.8°N 12050
7628
63.3
15063
8420
55.9
18075
8766
48.5
24100
8772
36.4
Athens
38.0°N
8263
6610
80.0
10329
7695
74.5
12395
8490
68.5
16526
9271
56.1
Note: The over temperature protection tests have been carried out according to EN12976 with an irradiation higher than
20 MJ/m
2
/day. An over temperature protection device should be installed in the situation that irradiation this exposure
levels could be exceeded.
Содержание 151J
Страница 44: ...44 INSTALLATION DIAGRAMS MODELS 151J 181J 181LCSC 181BTC 151J 181J 181LCSC 181BTC J collector illustrated ...
Страница 45: ...45 INSTALLATION DIAGRAMS MODELS 151L 181L 151L 181L ...
Страница 46: ...46 INSTALLATION DIAGRAMS MODELS 302J 302LCSC 302BTC 303J 302J 302LCSC 302BTC 303J J collectors illustrated ...
Страница 47: ...47 INSTALLATION DIAGRAMS MODELS 302L 303L 302L 303L ...
Страница 51: ...CONNECTION DETAILS 51 With Pitch Tiled Roof Mounting ...
Страница 58: ...58 This page is intentionally blank ...
Страница 59: ...59 This page is intentionally blank ...