Procedure
Step 1
Remove cable glands from the positive and negative connectors.
Figure 4-25 Connecting DC input power cables
Step 3
Insert the positive and negative power cables into corresponding cable glands.
Step 5
Insert crimped power cables into corresponding housings until you hear a "click" sound.
The power cables snap into place.
End
Figure 4-26 Connecting DC input power cables
1. Positive power cable 2. Negative power cable
L2 is 2 to 3 mm longer than L1.
Note
Step 2
Remove the insulation layer with an appropriate length from the positive and negative
power cables by using a wire stripper as show in Figure 4-26.
Step 4
Insert the stripped positive and negative power cables into the positive and negative
metal terminals respectively and crimp them using a clamping tool. Ensure that the cables
arecrimped until they cannot be pulled out by force less than 400 N, as shown in Figure 4-27.
1. Positive power cable
2. Negative power cable
Step 6
Reinstall cable glands on positive and negative connectors and rotate them against the
insulation covers.
Step 7
Insert the positive and negative connectors into corresponding DC input terminals of
the Sofar 30~40KTL until you hear a "click" sound, as shown in Figure 4-28.
Figure 4-27 Connecting DC input power cables
1. Bayonet
All rights reserved
Shenzhen SOFARSOLAR Co ., Ltd.
C
39
All rights reserved
Shenzhen SOFARSOLAR Co ., Ltd.
C
40
User manual
User manual
Electrical Connections
Electrical Connections
Sofar 30K~40KTL
Sofar 30K~40KTL
Document Version 1.0(2015.08.06)
Document Version 1.0(2015.08.06)
Компания
«
Реалсолар
»,
Санкт
-
Петербург
,
Октябрьская
наб
.,
д
. 104,
к
. 1,
лит
.
П
www.realsolar.ru +7911-921-52-96