7. Troubleshooting
This section contains information and procedures for solving possible problems
with the inverter.
This section help users to identify the inverter fault. Please read the
following procedures carefully:
Check the warning, fault messages or fault codes shown on the inverter
screen, record all the fault information.
If there is no fault information shown on the screen, check whether the
following requirements are met:
- Is the inverter mounted in a clean, dry place with good ventilation?
- Is the DC switch turned ON?
- Are the cables adequately sized and short enough?
- Are the input and output connections and wiring in good condition?
- Are the configuration settings correct for the particular installation?
- Are the display panel and the communication cables properly connected and
undamaged?
Follow the steps below to view recorded problems: Press "Back" to enter
the main menu in the normal interface. In the interface screen select "Event
List", then press "OK" to enter events.
Earth Fault Alarm
This inverter complies with AS/NZS 5033 for earth fault alarm monitoring.
If an Earth Fault Alarm occurs, the fault will be displayed on the LCD screen,
the red light will be on, and the fault can be found in the history of the fault.
For the machine installed with Wi-Fi/GPRS, the alarm information can be
seen on the corresponding monitoring website, and can also be received by the
APP on the mobile phone.
When the inverter is connected to the battery system, when the battery system
has ground fault/leak alarm in accordance with AS/NZS 5139, the inverter will
also alarm. The alarm method is the same AS above.