HYD 3K~6K-EP

User manual

Copyright © Shenzhen SOFARSOLAR Co., Ltd

- 28 -

2. RS485

Wired monitoring or inverter cascade monitoring

Refer to the figure shown below, connect the RS485+ and RS485- of the inverter to
the TX+ and TX- of the RS485

USB adapter, and connect the USB port of the

adapter to the computer. (NOTE

The length of the RS485 communication cable

should be less than 1000 m)

Fig 4-10

RS485 wires are connected in parallel between inverters, (NOTE

When multiple

inverters are connected via RS485 wires, set communication address to

differentiate the inverters

please refer to this manual<6.3.1System

setting

8.Communication Addr>)

Fig.4-11 RS485 connection(cascade of monitoring between inverters)

3. Logic interface

The logic interface pin definitions and circuit connections are as follows:

Logic interface pin are defined according to different standard requirements

a

Logic interface for AS/NZS 4777.2:2020, also known as inverter demand

response modes (DRMs).

The inverter will detect and initiate a response to all supported demand response

commands within 2 s. The inverter will continue to respond while the mode

remains asserted.

Table 4-6 Function description of the DRMs terminal

Содержание HYD 3000-EP

Страница 1: ...nment 13 3 5 Determining the Installation Position 13 3 6 Moving the HYD 3K 6K EP 15 3 7 Installing HYD 3K 6K EP 15 4 Electrical Connections 17 4 1 Wire instructions 18 4 2 Connecting PGND Cables 18 4 3 PV Connection 20 4 4 Battery Connection 21 4 5 Load connection 22 4 6 Grid connection 23 4 7 External communication interface 25 5 Buttons and indicator lights 36 5 1 Buttons 36 5 2 Indicator light...

Страница 2: ...ther user or field Copyright Declaration The copyright of this manual belongs to Shenzhen SOFARSOLAR Co Ltd Any corporation or individual should not plagiarize partially copy or fully copy it including software ect and no reproduction or distribution of it in any form or by any means All right reserved SOFARSOLAR reserves the right of final interpretation This manual is subject to change according...

Страница 3: ...nd troubleshooting of HYD 3K 6K EP inverters HYD 3000 EP HYD 3680 EP HYD 4000 EP HYD 4600 EP HYD 5000 EP HYD 5500 EP HYD 6000 EP Keep this manual where it will be accessible at all times Target Group This manual is intended for qualified electrical technical personnel who are responsible for inverter installation and commissioning in the PV power system and PV plant operator Symbols Used This manu...

Страница 4: ...hazardous situation which if not avoided could result in death or serious injury Warning Caution indicates a hazardous situation which if not avoided could result in minor or moderate injury Caution Attention indicates potential risks which if not avoided may lead to equipment fault or property damage Attention Note provides tips that are valuable for the optimal operation of the product Note ...

Страница 5: ...ner box OFF to cut off the high voltage DC When the battery needs to be installed please confirm the positive and negative terminals of the battery and turn OFF the battery Otherwise serious injury may be caused Qualified persons The customer must make sure the operator has the necessary skill and training to do his her job Staff in charge of using and maintaining the equipment must be skilled awa...

Страница 6: ...cessary Transport of the equipment especially by road must be carried out with by suitable ways and means for protecting the components in particular the electronic components from violent shocks humidity vibration etc Labels on the equipment Electric connection Please comply with all the current electrical regulations about accident prevention in dealing with the solar invert Before the electrica...

Страница 7: ...oves Attention Maintenance and repair Before any repair work turn OFF the AC circuit breaker between the inverter and electrical grid first then turn OFF the DC switch After turning OFF the AC circuit breaker and DC switch wait for 5 minutes at least before carrying out any maintenance or repair work Danger Inverter should work again after removing any faults If you need any repair work please con...

Страница 8: ...rotect the PV system and personnel security Attention Ensure input DC voltage Max DC voltage Over voltage may cause permanent damage to inverter or other losses which will not be included in warranty Warning Signs on the inverter There are some symbols which are related to security on the inverter Please read and understand the content of the symbols and then start the installation This symbol ind...

Страница 9: ...EC standard 70 1 EN 60529 June 1997 Positive pole and negative pole of the input voltage DC This side up HYD 3K 6K EP inverter must always be transported handled and stored in such a way that the arrows always point upwards RCM Regulatory Compliance Mark The product complies with the requirements of the applicable Australian standards ...

Страница 10: ... 3K 6K EP inverter has a variety of built in operating modes to suit the diverse user needs The HYD 3K 6K EP inverter can provide a complete solution in the period of rising energy costs such as oil and coal the energy subsidy of photovoltaic grid connected system keeps falling In the period of continuous power supply and emergency power supply demand in mountainous areas or base stations without ...

Страница 11: ... as air conditioners or refrigerators with an automatic switchover time of less than 10 milliseconds a Dual MPP trackers with 1 5 DC overload b Flexible switching between grid tied mode and energy storage mode c Max battery charge and discharge efficiency 94 6 d 1 strings of battery input with maximum 100A charge and discharge current e Wide battery voltage range 90 580V f AC Multi parallel functi...

Страница 12: ...HYD 3K 6K EP User manual Copyright Shenzhen SOFARSOLAR Co Ltd 8 Fig 2 3 Electrical block diagram ...

Страница 13: ...g Deliverables After unpacking the inverter check whether deliverables are intact and complete If any damage is found or any component is missing contact the dealer Table3 1 Components and mechanical parts that should be delivered NO Picture Description Quantity 1 Inverter 1pcs Do NOT install the HYD 3K 6K EP on flammable material Do NOT install the HYD 3K 6K EP in an area used to store Flammable ...

Страница 14: ... cables 2pcs 6 Metal terminals secured to PV input power cables 2pcs 7 BAT input terminal 1pcs 8 BAT input terminal 1pcs 9 M6 Hexagon screws 3pcs 10 M8 80 Expansion bolts used to secure the wall mount bracket to the wall 4pcs 11 AC Grid connector 1pcs 12 Load Output connector 1pcs 13 Link port connector 1pcs 14 8 pin terminal Matching terminal resistance parallel system 1pcs ...

Страница 15: ...onic type guide rail mounting electric energy meter 1pcs optional 19 Manual 1pcs 20 The warranty card 1pcs 21 Quality Certificate 1pcs 3 2 Product Overview HYD 3K 6K EP inverter is 100 strictly inspected before package and delivery It is forbidden to put the HYD 3K 6K EP inverter upside down during delivery CAUTION Please check the product package and fittings carefully before installation ...

Страница 16: ... port 5 Link Port 0 10 LCD 3 3 Tools Prepare tools required for installation and electrical connections Table 3 3 Tools required for installation and electrical connections NO Tool Model Function 1 Hammer drill Recommend drill dia 6mm Used to drill holes on the wall 2 Screwdriver Wiring 3 Cross screwdriver Remove and install AC terminal screws 4 Removal tool Remove PV terminal 5 Wire stripper Stri...

Страница 17: ...5 Anti dust respirator Operators wear 3 4 Installation Environment a Choose a dry clean and tidy place convenient for installation b Ambient temperature range 25 60 c Relative humidity 0 100 non condensed d HYD 3K 6K EP inverter shall be installed in a well ventilated place e No flammable or explosive materials close to HYD 3K 6K EP inverter f The AC overvoltage category of HYD 3K 6K EP inverter i...

Страница 18: ...HYD 3K 6K EP User manual Copyright Shenzhen SOFARSOLAR Co Ltd 14 Fig 3 3 Installation Position of HYD 3K 6K EP inverter ...

Страница 19: ...rotect its shell Attention 3 7 Installing HYD 3K 6K EP Step 1 Determine the positions for drilling holes ensure the hole positions are level then mark the hole positions using a marker pen use the hammer drill to drill holes on the wall ApertureΦ10 mm When drilling keep the impact drill perpendicular to the wall and drill slightly deeper than the length of the expansion pipe After drilling please ...

Страница 20: ...HYD 3K 6K EP User manual Copyright Shenzhen SOFARSOLAR Co Ltd 16 Fig 3 5 Installing HYD 3K 6K EP ...

Страница 21: ...glasses and boots when working on high voltage high current systems such as inverter and battery systems Attention PV modules generate electric energy when exposed to sunlight and can create an electrical shock hazard Therefore before connecting DC input power cable cover PV modules using opaque clot Danger For HYD 3K 6K EP open circuit voltage Voc of module arrays connected in series must be 580V...

Страница 22: ...e electrode of lithium battery Outdoor multi core copper cable Conductor cross sectional area 16mm2 20mm2 Connect the negative electrode of lithium battery Connect the positive electrode of photovoltaic cell Industry common outdoor photovoltaic cable Conductor cross sectional area 4mm2 6mm2 Connect the negative electrode of photovoltaic cell Load L Outdoor multi core copper cable Conductor cross s...

Страница 23: ... layer with an appropriate length using a wire stripper as shown in Fig 4 1 Step 2 Insert the exposed core wires into the OT terminal and crimp them by using a crimping tool as shown in Fig 4 1 Step 3 Install the crimped OT terminal flat washer using M5 screw and tighten the screw to a torque of 3 N m using an Allen wrench Note 1 L3 is the length between the insulation layer of the ground cable an...

Страница 24: ...the cables are crimped until they cannot be pulled out by force less than 400 N as shown in Fig Step 4 Insert crimped power cables into corresponding housings until you hear a click sound The power cables snap into place Step 5 Reinstall cable glands on positive and negative connectors and rotate them against the insulation covers Step 6 Insert the positive and negative connectors into correspondi...

Страница 25: ...HYD 3K 6K EP User manual Copyright Shenzhen SOFARSOLAR Co Ltd 21 Disconnect PV connectors 4 4 Battery Connection Fig 4 3 Install battery connection ...

Страница 26: ...n Cross screwdriver Connect the brown wire to the hole labeled L fasten the wire using an Cross screwdriver Connect the blue wire to the hole labeled N fasten the wire using an Cross screwdriver Step 4 Insert the load connector and hear click then tighten the waterproof nut at the instantaneous value as shown in the figure below to ensure that the cable is firmly connected Step 5 Connect the conne...

Страница 27: ...A or higher is suggested Procedure Step 1 Select the appropriate cable type and specifications according to the table4 3 Refer to Fig for processing wire Step 2 Pass the wire through the terminal as shown in Fig Step 3 According to the mark lock the wire into the keyhole on the terminal and tighten it with the hexagon socket wrench as shown in Fig Step 4 Push the terminal forward until the sound o...

Страница 28: ...rward until the sound of click is heard and the terminal connection is completed as shown in Fig If you need to remove the terminals from the machine use the tool to press on the direction indicated by the big arrow and pull the terminals out Need to dismantle the end connection to use the tool as shown in figure attending Fig 4 5 Load connection A 30 50mm B 3 5mm ...

Страница 29: ...SB WIFI communication interface Fig 4 6 USB WIFI communication interface Table 4 4 Interface description PIN Definition Function Note 1 GND S USB power The USB power supply is 5V 1A Cannot be used for external device charging 2 DP USB data 3 DM USB data 4 VBUS USB power Refer to the figure shown below Fig 4 7 ...

Страница 30: ...it the https doc solarmanpv com web 7 SolarMAN App User Manual Please visit the https doc solarmanpv com web 14 4 7 2 COM Multifunction communication interface Table 4 5 Interface description PIN Definition Function Note 1 CANH CAN high data Communication with lithium battery BMS the inverter CAN be adaptive to lithium battery BMS to provide CAN communication and RS485 communication 2 CANL CAN low...

Страница 31: ...rent sensor outputs a positive electrode 15 RS485 B RS485 differential signal Meter communication 16 RS485 A RS485 differential signal Fig 4 9 COM interface 1 BMS Communication with lithium battery BMS Connect the CAN RS485 input for communication between the inverter and battery ...

Страница 32: ...485 wires set communication address to differentiate the inverters please refer to this manual 6 3 1System setting 8 Communication Addr Fig 4 11 RS485 connection cascade of monitoring between inverters 3 Logic interface The logic interface pin definitions and circuit connections are as follows Logic interface pin are defined according to different standard requirements a Logic interface for AS NZS...

Страница 33: ...ble 4 7 Function description of the terminal Pin NO Pin name Description Connected to RRCR 8 L1 Relay contact 1 input K1 Relay 1 output 9 L2 Relay contact 2 input K2 Relay 2 output 10 L3 Relay contact 3 input K3 Relay 3 output 11 L4 Relay contact 4 input K4 Relay 4 output 7 G GND Relays common node Table 4 8 The inverter is preconfigured to the following RRCR power levels close is 1 open is 0 L1 L...

Страница 34: ...tive Power Power drop rate Cos φ 1 0 5 seconds 1 0 100 1 4 Meter CT PIN15 and PIN16 are used for meter communication the electricity meter is shown in the fig PIN15 and PIN16 correspond to 7 8 respectively on the electricity meter as shown in fig The connection mode is shown in fig The 1 2 and 3 4 on the electricity meter are connected to voltage signals L and N respectively And the current needs ...

Страница 35: ...ower limit on the menu interface of the machine The hard anti reverse current setting requires permission Only the installer and the device vendor have the permission to use the Bluetooth APP for setting enabling disabling Settings and setting the Reflux Power limit Refer to 6 3 2 Advanced setting 2 Anti Reflux in this manual for specific operation methods To obtain grid information via Plan B Wir...

Страница 36: ...ol and Anti Reflux Control can be used together However when Hard Anti Reflux control is enabled Anti Reflux power limit cannot exceed the Hard Anti Reflux power limit The limit value is reported to overload protection When communication signal with the electricity meter is lost the output power of the inverter is limited to the value of soft export limit and does not enter the state of fault prot...

Страница 37: ...HYD 3K 6K EP User manual Copyright Shenzhen SOFARSOLAR Co Ltd 33 Fig 4 15 Electrical connections Plan A CT default ...

Страница 38: ...HYD 3K 6K EP User manual Copyright Shenzhen SOFARSOLAR Co Ltd 34 Fig 4 16 Electrical connections Plan B Meter CT optional ...

Страница 39: ...l to each machine shall be consistent with the specification of the cable length so as to ensure that the loop impedance is consistent and the current of the LOAD current diverted to each machine is nearly equal 3 When the total power of AC Load is greater than 110 of the rated power of the machine For example one inverter AC LOAD has a maximum allowable power of 5 5kVA and six parallel machines A...

Страница 40: ...or enter the main interface press Up to the upper menu option or value plus 1 press Down to the lower menu option or value minus 1 Press OK to select the current menu option or switch to the next digit 5 2 Indicator lights and status Status On Grid Green light Off Grid Green light Alarm Red light On grid ON Standby On Grid Flashing Off Grid ON Standby Off Grid Flashing Alarm ON ...

Страница 41: ...t breaker OFF 7 AC circuit breaker is correctly connected between inverter LOAD port critical load circuit breaker OFF 8 For lithium battery please ensure that the communication cable has been correctly connected 6 2 Starting up and shutting down the inverter IMPORTANT PLEASE FOLLOW THE FOLLOWING PROCEDURE to switch ON HYD ES inverter 1 Turn ON PV switch 2 Switch ON the battery 3 Turn ON AC circui...

Страница 42: ...ode files and confirm the import Mobile APP to import online After the professional operator connects the machine to Bluetooth through the mobile APP select the corresponding name of safety regulation in the APP guide function to import the file This operation is only authorized by the installer and the equipment manufacturer and cannot be operated by the end customer Once the country is set it is...

Страница 43: ...7 000 Croatia 012 000 Poland 108 000 Lithuania 013 000 Austria Tor Erzeuger 014 000 Japan 018 000 EU EN50438 001 EU EN50549 019 000 IEC EN61727 020 000 Korea 021 000 Sweden 022 000 Europe General For Australian Market For compliance with AS NZS 4777 2 2020 please select from 002 000 Australia A Australia Region A 002 008 Australia B Australia Region B 002 009 Australia C Australia Region C Please ...

Страница 44: ... regions are shown in the following table Region Default value VW1 VW2 Australia A Voltage 253V 260V Inverter maximum active power output level P of Srated 100 20 Australia B Voltage 250V 260V Inverter maximum active power output level P of Srated 100 20 Australia C Voltage 253V 260V Inverter maximum active power output level P of Srated 100 20 Default volt var settings for different regions are s...

Страница 45: ...ation protocol Lead acid or no protocol type 1 Battery Address 1 Battery Capacity 2 Battery Charge Current Limit 2 Battery Nominal Voltage 3 Battery Discharge Current Limit 3 Battery Cell Type 4 Battery DOD EOD 4 Battery Charge Current Limit 5 Battery Discharge Current Limit 6 Battery DOD EOD Table 6 2 Default values for other Settings Item The default state Energy Storage Mode Self use mode EPS M...

Страница 46: ... monitoring page to modify the mode and parameters of the machine and the corresponding instructions need to be provided by internal professionals 6 3 Menu Fig 6 1 Main interface In the main interface press Down button to enter grid battery parameters page Main interface Down Grid Output Information Grid V V AC Current A Frequency Hz Battery Information 1 Batt V V Down Batt Chrs Curr A Batt DisChr...

Страница 47: ... Software Update 6 3 1 System setting 1 System Setting OK 1 Language Settings 2 Time 3 Safety Param 4 Energy Storage Mode 5 Auto Test Only for Italy 6 EPS Mode 7 Communication Addr 1 Language Settings Used to set the menu display language 1 Language Settings OK 1 中文 OK 2 English 3 Italiano 4 2 Time Set the system time for the inverter 2 Time OK Time 2020 05 13 17 07 00 3 Safety Param User can modi...

Страница 48: ...use mode inverter will automatically charge discharge the battery 1 If PV generation LOAD consumption ΔP 100W inverter won t charge or discharge the battery 2 If PV generation LOAD consumption the surplus power will be stored in the battery 3 If the battery is full or already at Max Charge Power excess power will be exported to the grid 4 If PV generation LOAD consumption it will discharge the bat...

Страница 49: ...stem can produce more electricity than your home electricity consumption Then you don t need to set an off peak charge period to charge your battery in summer at all You can select an effective date normally winter for Time of use mode in this case Outside the effective date inverter is working in Auto Mode You can set multiple Time of use rules to meet your more complex requirement Right now we s...

Страница 50: ... 5 Auto Test ONLY for Italian Market 5 Auto Test OK 1 Autotest Fast 2 Autotest STD Autotest Fast 1 Autotest Fast OK Start Autotest Press Ok to start Testing 59 S1 Wait Test 59 S1 OK Wait Testing 59 S2 Wait Test 59 S2 OK Wait Testing 27 S1 Wait Test 27 S1 OK Wait Testing 27 S2 Wait Test 27 S2 OK Wait Testing 81 S1 Wait Test 81 S1 OK Wait Testing 81 S2 Wait Test 81 S2 OK Wait Testing 81 S1 Wait Test...

Страница 51: ...s Down 27 S2 227V 205ms Press Down 81 S1 threshold 50 5Hz 100ms Press Down 81 S1 49 9Hz 103ms Press Down 81 S2 threshold 51 5Hz 100ms Press Down 81 S2 49 9Hz 107ms Press Down 81 S1 threshold 49 5Hz 100ms Press Down 81 S1 50 0Hz 105ms Press Down 81 S2 threshold 47 5Hz 100ms Press Down 81 S2 50 1Hz 107ms Autotest STD 2 Autotest STD Press OK to start The test procedure is same as Autotest Fast but it...

Страница 52: ...er will discharge battery 4 If PV generation is normal but LOAD consumption 0 the surplus power will be stored in the battery 7 Communication Addr 7 Communication Addr OK 1 Communication Addr OK 2 Baud Rate OK 6 3 2 Advanced setting 2 Advanced setting OK Input 0001 1 Battery Parameter 2 Anti Reflux 3 IV Curve Scan 4 Logic interface 5 Factory Reset 6 Parallel setting 7 Bluetooth Reset 8 CT Calibrat...

Страница 53: ...ode if EPS mode is enabled keep discharging the battery till battery SOC is less than 20 7 Depth of Discharge OK Discharge Depth 50 EPS Discharge Depth 80 EPS Restore Depth 20 2 Anti Reflux The user can enable Anti Reflux Control to limit the max export power to grid Reflux Power set is desired max export power to grid Refer to 4 7 2 for connection of the system when using Anti Reflux function 2 A...

Страница 54: ...tion method of the parallel system 6 Parallel setting OK 1 Parallel Control 2 Parallel Primary Replica 3 Parallel Address 4 Save 1 Parallel Control Enable or disable parallel functions Both the master and the slave must enable this function 2 Parallel Primary Replica Set up the Primary and Replica Select one inverter as the Primary and set the others to Replica 3 Parallel Address Set the parallel ...

Страница 55: ...OK Today PV KWH Load KWH Export KWH Import KWH Charge KWH Discharge KWH Down Month PV KWH Load KWH Export KWH Import KWH Charge KWH Discharge KWH Down Year PV KWH Load KWH Export KWH Import KWH Charge KWH Discharge KWH Down Lifetime PV KWH Load KWH Export KWH Import KWH Charge KWH Discharge KWH 6 3 4 System information 4 System information OK 1 Inverter Info 2 Battery Info 3 Safety Param 1 Inverte...

Страница 56: ...PS Mode Down Inverter Info 4 IV Curve Scan Logic Interface Control PF Time Setting QV Time Setting Down Inverter Info 5 Power Factor Anti Reflux Insulation resistance 3 Safety Param OK Safety Param 1 OVP 1 OVP 2 UVP 1 UVP 2 Down Safety Param 2 2 Battery Info OK Battery1 2 info 1 Battery Type Battery Capacity Over V Protection Discharge Depth Down Inverter1 2 Info 2 Max Charge A Max Charge V Max Di...

Страница 57: ...0 4 3 14 11 45 OK 1 ID001 GridOVP 2 ID005 2020 4 3 11 26 38 2 ID005 GFCI 6 3 6 Software Update HYD 3K 6K EP inverters offer software upgrade via USB Disk drive to maximize inverter performance and avoid inverter operation error caused by software bugs Upgrade file folder name is firmware HYD EP The three upgrade file names are HYD EP_ARM bin HYD EP_DSPM bin HYD EP_DSPS bin Step 1 Insert the USB Di...

Страница 58: ...r help USB Fault MDSP File Error SDSP File Error ARM File Error Update DSP1 Fail Update DSP2 Fail Update ARM Fail Step 8 After the update is completed turn off the DC breaker wait for the LCD screen extinguish then restore the WiFi connection and then turn on the DC breaker and AC breaker again the inverter will enters the running state User can check the current software version in Systemlnfo Sof...

Страница 59: ...ings correct for the particular installation Are the display panel and the communication cables properly connected and undamaged Follow the steps below to view recorded problems Press Back to enter the main menu in the normal interface In the interface screen select Event List then press OK to enter events Earth Fault Alarm This inverter complies with AS NZS 5033 for earth fault alarm monitoring I...

Страница 60: ...oltage over frequency under frequency protection points after obtaining approval from the local electrical grid operator ID002 GridUVP The grid voltage is too low ID003 GridOFP The grid frequency is too high ID004 GridUFP The grid frequency is too low ID005 GFCI Charge Leakage Fault Internal faults of inverter switch OFF inverter wait for 5 minutes then switch ON inverter Check whether the problem...

Страница 61: ... PvConfigError Error setting input mode Check the PV input mode parallel independent mode Settings for the inverter If not change the PV input mode ID045 CTDisconnect CT error Check whether the CT wiring is correct ID048 FanFault FanFault Please check whether the fan 1 of inverter is running normally ID049 TempFault_Bat Battery temperature protection Make sure the inverter is installed where there...

Страница 62: ...te ID070 BatOVP Battery over voltage Check whether the battery overvoltage setting is inconsistent with the battery specification ID071 LLCBusOVP LLC BUS overvoltage protection Internal faults of inverter switch OFF inverter wait for 5 minutes then switch ON inverter Check whether the problem is solved If no please contact technical support ID072 SwBusRmsOVP Inverter bus voltage RMS software overv...

Страница 63: ...atLowVoltageS hut Battery low voltage shutdown ID129 unrecoverHwAc OCP Output hardware overcurrent permanent failure Internal faults of inverter switch OFF inverter wait for 5 minutes then switch ON inverter Check whether the problem is solved If no please contact technical support ID130 unrecoverBusOV P Permanent Bus overvoltage failure ID131 unrecoverHwBus OVP Permanent Bus hardware overvoltage ...

Страница 64: ...r CAN communication is recommended Check the communication line or port of the battery and inverter for faults ID161 ForceShutdown Force shutdown The inverter is performed a forced shutdown ID162 RemoteShutdown Remote shutdown The inverter is performed a remote shutdown ID163 Drms0Shutdown Drms0 shutdown The inverter is performed with a Drms0 shutdown ID165 RemoteDerating Remote derating The inver...

Страница 65: ...ase clean the inverter with an air blower a dry soft cloth or a soft bristle brush Do NOT clean the inverter with water corrosive chemicals detergent etc Heat sink cleaning For the long term proper operation of inverters ensure there is enough space around the heat sink for ventilation check the heat sink for blockage dust snow etc and clean them if they exist Please clean the heat sink with an ai...

Страница 66: ...e Lithium ion Lead acid Nominal battery voltage 48V Battery voltage range 42 58V Battery capacity 50 2000Ah Maximum charging discharging power 3750W 4000W 4250W 5000W 5000W 5000W 5000W Maximum charging current 75A 80A 85A 100A 100A 100A 100A Maximum discharging current 75A 80A 85A 100A 100A 100A 100A Depth of discharge 0 90 DOD adjustable Lithium ion Charging curve BMS Lithium ion Communication CA...

Страница 67: ...Wp 6900Wp 7500Wp 7500Wp 9000Wp Max DC power for single MPPT 3500W 3500W 3500W 3500W 3750W 3750W 4500W Max input voltage 600V Rated input voltage 360V Start up voltage 100V MPPT operating voltage range 90 580V Full power MPPT voltage range V 160 520 180 520 200 520 230 520 250 520 250 520 300 520 Number of MPP trackers 2 Max input current per MPPT 13A 13A Isc PV absolute maximum 18A 18A Maximum inv...

Страница 68: ...rent from utility grid 27 3A 32A 36 4A 41 8A 43 4A 43 4A 54 6A Output Current inrush 55A 2uS 55A 2uS 55A 2uS 55A 2uS 55A 2uS 55A 2uS 55A 2uS Rated apparent power VA 3600VA 4400VA 4800VA 5520VA 6000VA 6000VA 6000VA Maximum output fault current 32 5A 10 uS 34 5A 10 uS 35 25A 10uS 43A 10uS 43A 10uS 44A 10uS 48A 10uS Maximum output overcurrent protection 30 5A 10uS 32 5A 10uS 33 25A 10uS 41A 10uS 41A ...

Страница 69: ... 5000 EP HYD 5500 EP HYD 6000 EP Max apparent power VA 3000 3680 4000 4600 5000 5000 5000 Peak output power Duration 3600VA 60s 4400VA 60s 4800VA 60s 5520VA 60s 6000VA 60s 6000VA 60s 6000VA 60s Max output current 13 6A 16A 18 2A 20 9A 22 7A 22 7A 22 7A Nominal voltage Frequency L N PE 220V 230V 240V 50 60Hz THDv Liner load 3 Switch time 10ms default ...

Страница 70: ... inverter 97 2 97 2 97 2 97 3 97 3 97 3 97 5 Max efficiency of solar inverter 97 6 97 6 97 6 97 8 97 8 97 8 98 0 Max charging efficiency of battery 94 6 Max discharging efficiency of battery 94 6 DC switch Yes PV reverse polarity protection Yes Over current protection Yes Over voltage protection Yes PV insulation detection Yes Ground fault monitoring Yes Firm frequency response function Optional S...

Страница 71: ... Weight 21 5kg Inverter topology High frequency insolation for bat Protective class I II or III DC side overvoltage II AC side overvoltage III Active anti islanding method Reactive Power Disturbance Standby self consumptio n 10W Ambient temperature range 30 60 Above 45 Derating Allowable relative humidity range 0 100 Noise 25dB Max operating altitude 2000m Cooling Natural Degree of protection IP65...

Страница 72: ...cation Bluetooth RS485 WIFI GPRS optional Parallel operation YES Warranty 10 years Grid standards VDE AR N 4105 VDE V 0126 1 1 AS NZS 4777 CEI 0 21 G98 G99 TR321 TR322 EN 50438 EN50549 UTE C15 712 1 NRS 097 2 1 UNE 206 007 1 Safety standards IEC 62109 1 2 IEC 62040 1 IEC 62116 IEC 61727 IEC 61683 IEC 60068 1 2 14 30 EMC EN 61000 6 2 EN 61000 6 3 EN 61000 3 2 EN 61000 3 3 EN 61000 3 11 EN 61000 3 1...

Страница 73: ...ans Schedule 2 to the Competition and Consumer Act 2010 Cth b Claim means any judgment claim demand action suit or proceeding for damages debt restitution equitable compensation account injunctive relief specific performance or any other remedy whether by original claim cross claim or otherwise whether arising at common law in equity under statute or otherwise wherever arising whether known or unk...

Страница 74: ...Our goods come with guarantees that cannot be excluded under the ACL You are entitled to a replacement or refund for a major failure and for compensation for any other reasonably foreseeable loss or damage You are also entitled to have the goods repaired or replaced if goods fail to be of acceptable quality and the failure does not amount to a major failure Subject to any statutory rights which ca...

Страница 75: ...e 1 freight to the End User labour and material necessary to regain a faultless functioning Product The Factory warranty does not cover without limitation Consequential Loss repair reimbursement costs transport costs travel costs accommodation cost of SOFARSOLAR personnel as well as any costs of associated third party staff and personnel Express delivery costs will not be covered In the event SOFA...

Страница 76: ...wnership of the supplied replacement Product s until the purported faulty or otherwise defective Product has been received in accordance with these terms and conditions The End User may contact the dealer SOFARSOLAR authorised dealer or distributor or installer if the Product is faulty or otherwise defective All other purported costs including but not limited to compensation from any direct or ind...

Страница 77: ...ils refuses or otherwise neglects to strictly follow any applicable user manual installation guide and maintenance regulations supplied with the Product including not ensuring sufficient ventilation for the Product as described in SOFARSOLAR installation guide Defects faults cosmetics or rendered non functional damage caused by unforeseen circumstances or force majeure event including but not limi...

Страница 78: ...ce breach of duty as bailee or the wilful act or default of SOFARSOLAR c These Terms and Conditions shall not exclude or limit the application of any provisions of any statute including any implied condition or warranty the exclusion of which would contravene any statute including the ACL or cause any part of this clause 4 to be illegal invalid void or unenforceable d If the exclusion of liability...

Страница 79: ...warranty the End User must provide the following information and documentation of the faulty or otherwise defective Product Product Model and serial number A copy of the valid purchasing invoice Fault descriptions and error IDs where applicable End user and or claimant details Detailed information about the entire system module PV system diagram installation date etc Documentation of previous clai...

Страница 80: ...discretion may charge fees to the End User including without limitation a On site service fee cost of travel and time for the technician to deliver on site service and labour cost for the technician who is repairing performing maintenance on installing hardware or software and debugging the faulty product b Parts materials fee cost of replacement parts materials including any shipping admin fee th...

Отзывы: