HYD 3K~6K-EP
User manual
Copyright © Shenzhen SOFARSOLAR Co., Ltd
- 41 -
Australia C
Voltage
215V
230V
240V
255V
Inverter reactive power
level (Q) % of
S
rated
44%
supplying
0%
0%
60%
supplying
It’s very important to make sure that you have selected the correct
country code according to requirements of local authority.
Please consult qualified electrical engineer or personnel from electrical
safety authorities about this.
Shenzhen SOFARSOLAR Co., Ltd. is not responsible for any
consequences arising out of incorrect country code selection.
Caution
*4. Set battery parameters (Take the default input channel configuration as an
example). Start with battery 1 and work your way up to battery n.
Battery Type
Type of band
communication protocol
Lead acid or no protocol
type
1.Battery Address
1.Battery Capacity
2.Battery Charge Current
Limit
2.Battery Nominal Voltage
3.Battery Discharge
Current Limit
3.Battery Cell Type
4.Battery DOD(EOD)
4.Battery Charge Current
Limit
5.Battery Discharge Current
Limit
6.Battery DOD(EOD)
Table 6-2 Default values for other Settings
Item
The default state
Energy Storage Mode
Self-use mode
EPS Mode
Disable
Anti Reflux
Disable
IV Curve Scan
Disable
Logic interface
Disable
Setting power quality response modes
The setting and viewing method of power quality response mode and power grid
protection.
The setting and viewing of these two functions require professional and technical
personnel to conduct them by issuing and transmitting instructions on the remote
monitoring platform, on the premise that the data acquisition rod is installed
(WiFi/GPRS/Ethernet). End customers cannot modify by themselves.