HYD 3K~6K-EP
User manual
Copyright © Shenzhen SOFARSOLAR Co., Ltd
- 23 -
③
④
⑤
⑥
⑦
4.6. Grid connection
SOFARSOLAR has already integrated RCMU (residual current monitoring unit)
inside inverter, If an external RCD is required, a type-A RCD with rated residual
current of 100mA or higher is suggested.
Procedure
:
Step 1
Select the appropriate cable type and specifications according to the
table4-3. Refer to Fig.
①
for processing wire.
Step 2
Pass the wire through the terminal, as shown in Fig.
②
.
Step 3
According to the mark, lock the wire into the keyhole on the terminal and
tighten it with the hexagon socket wrench, as shown in Fig.
③④
.
Step 4
Push the terminal forward until the sound of "click" is heard, as shown in
Hold the button
to unlock