HYD 3K~6K-EP
User manual
Copyright © Shenzhen SOFARSOLAR Co., Ltd
- 50 -
3.Force Scan
OK
4.
Logic interface Control
Enable or disable logical interfaces. Please refer to this manual 4.7.2, inverter logic
interface connection for details.
4.Logic interface Control
OK Enable
OK
Disable
OK
5.
Factory Reset
5.Factory Reset
OK 1.Clear Energy Data
OK
2.Clear Events
OK
Clean the inverter of the total power generation.
1.Clear Energy Data
OK Input password
OK
Input 0001
Clean up the historical events recorded in the inverter.
2..Clear Events
OK Clear Events?
OK
6.
Parallel setting
Please refer to <4.7.3 Link Port 0&1-Cascade communication interface> for the
connection method of the parallel system.
6.Parallel setting
OK 1.Parallel Control
2.Parallel Primary-Replica
3.Parallel Address
4.Save
1
.
Parallel Control: Enable or disable parallel functions. Both the master and the
slave must enable this function.
2
.
Parallel Primary-Replica: Set up the Primary and Replica. Select one inverter as
the Primary and set the others to Replica.
3
.
Parallel Address: Set the parallel address. Each inverter needs to set a parallel
address, and the parallel address in a parallel system cannot be repeated.
(
NOTE:
The parallel address is different from the communication address used for
monitoring.
)
4
.
Save: Save after the setup is complete.
7. Bluetooth Reset
7.Bluetooth Reset
OK
Please confirm! OK Success
8. CT Calibration
To calibrate the direction and phase of the CT, the battery should be charged or
discharged when using this function.