HYD 3K~6K-EP
User manual
Copyright © Shenzhen SOFARSOLAR Co., Ltd
- 31 -
③
④
If you need to use the CT alone, attach the CT to PIN13 and PIN14.
Generation and Export Limit Control functions for the inverter are available but
require the use of an external measurement device to obtain grid information.
There are 2 ways to obtain grid information:
Plan A: CT (default)
Plan B: Meter + CT (optional)
Note: CT and Meter is supplied separately to the inverter. Contact
manufacturer/importer/distributor to order CT and/or Meter.
To obtain grid information via Plan A:
Connect the wires according to the wiring method as shown in Figure 4-15 Plan A,
and then enable Anti-Reflux Power function and set the Reflux Power limit on the
menu interface of the machine. The hard anti-reverse current setting requires
permission. Only the installer and the device vendor have the permission to use the
Bluetooth APP for setting, enabling/disabling Settings, and setting the Reflux
Power limit. Refer to <6.3.2 Advanced setting
2. Anti Reflux> in this manual for
specific operation methods.
To obtain grid information via Plan B:
Wiring according to the wiring method as shown in Figure 4-16 Plan B, and then
enable Anti-Reflux Power function and set the Reflux Power limit on the menu
interface of the machine. The setting of hard anti-reverse flow is the same as that of
Plan A. The electricity meter function will also need to be enabled via the menu
interface of the machine. Refer to <6.3.2 Advanced setting
2. Anti Reflux> in
this manual for specific operation methods.
Note:
Anti-Reflux Function = Export Limit function