17
en
G
lI
s
H
Green Po
wer 2.0 600 k
VA
- Ref.: INMGP2601410-GB_12
4. R
equiSiteS
4. 9. p
rotectIon
anD
cross
-
sectIon
of
battery
cables
Values are provided for a distance of 5 meters between Green Power 2.0 and the battery. (Battery mean current
while discharging – Please see § 4.6.2). Use double insulated cables BN4-F.
CAUTION: The size of protections depends on the power and back up time of the system. Protections other
than the ones defined below may cause electrical hazard or damage to the equipment.
exemple of Ur fuse battery protection
1
, block type 90 ah: sWl2500, XP12V3000
Max Power
UPs output
backup
time
branches
number
blocks
number
4
Ur fuse
number
size of Ur
fuse
Icc mini
batterie
5
socomec
code
min. cross-
section
2
600kVA
600 kW
5 min
4
43
2x2
700A T3
9800A
E045648
3 x 185
10 min
5
43
2x2
700A T3
12200A
E045648
3 x 185
600 kVA
540 kW
5 min
4
39
2x2
700A T3
9800A
E045648
3 x 185
10 min
5
39
2x2
700A T3
12200A
E045648
3 x 185
1
not standard Fuse protection FUSOMAT 4x630A Socomec, please contact us
2
H07 RN-F cabling for a 5 meters distance between the UPS and the battery
4
see 8.8.1
exemple of circuit breaker battery protection
Definition for 43 blocs
Green Power
2.0 Power
backup
time
number of
contact in serie size of breaker
Magnetic adjustment
Im = nxIn
Icc battery min.
5
600kW
≤15 min
2
NW20-HDC-E
3297A
3626A
5
end of life