13
en
G
lI
s
H
Green Po
wer 2.0 600 k
VA
- Ref.: INMGP2601410-GB_12
N
N
N
N
≥10 cm
≥10 cm
≥10 cm
N
N
N
≥10 cm
≥10 cm
≥10 cm
≥10 cm
N
N
N
N
N
4.3-1
4.3-2
4.3-3
N
N
N
4. 3. g
eneral
rules
for
cable
InstallatIon
on
tray
the cables must be in installed on trays when indicated in the following diagrams. the trays must be
positioned near to green power 2.0.
all metal and suspended ducts or those in raised flooring MuSt be connected to earth and to the
various cabinets.
do not expose control and power upS cables to
other equipment sensitive to the electromagnetic
field.
1
Control cables: connections between the cabinets and each unit, alarm
signals, remote mimic panel, connection to the BMS (Building Management
System), emergency stop, connection to generator.
Wrong installation.
4. R
equiSiteS
Mains Aux Mains
Battery
Load
Control
cables
1
Allowed installation.
risk of electromagnetic interference be-
tween battery cables and output cables.
Common
Mains
Load
Battery
Control
cables
1
Mains Aux Mains
Battery
Load
Control
cables
1
4. 4. e
lectrIcal
requIsItes
The installation and the system must comply with national plant regulations. The electrical distribution panel must
have a protection and sectioning system installed for the input mains and the auxiliary mains. If a differential switch
is installed on the mains power switch (optional), it must be inserted upstream from the distribution panel.
Correct installation.
Common
Mains
Load
Battery
Control
cables
1