HRX-OM-M090
Chapter 5 Display and setting of various functions
5.11
Anti-freezing function
HRS Series
5-28
5.11 Anti-freezing function
5.11.1 Anti-freezing
function
The product can prevent the circulating fluid from freezing during winter time.
If there is a possibility of the circulating fluid freezing due to changes in the
installation and operating environment (operating period and weather), set
the protection in advance.
z
If the circulating fluid temperature falls below 3
o
C
, the pump will start
operating automatically.
z
The heat generated by the pump operation will warm up the circulating
fluid.
When the circulating fluid temperature reaches 5
o
C
or higher, the pump
will stop operating automatically.
z
As a result, the circulating fluid maintains a temperature of between 3
o
C
and 5
o
C
, preventing freezing.
If the anti-freezing function is set, [RUN] lamp flashes for 2 sec. during
waiting (pump does not operate). The [RUN] lamp flashes at 0.3 sec.
intervals during the automatic operation of the pump. The default setting of
this function is “OFF”.
z
This function starts in stand-by condition (power supply switch is
ON).
z
Fully open the valve or manual bypass valve arranged by the
customer so that the circulating fluid can circulate when the pump
starts automatic operation.
z
In extremely cold weather conditions, the heat generated by the
pump as described above may not be enough to prevent freezing.
z
During the automatic operation, the pump does not stop even if you
press "RUN/STOP" key.
z
In an emergency, stop operation by shutting off the power supply.
Содержание Series HRS012-A
Страница 8: ...HRX OM M090 Contents HRS Series...
Страница 144: ...HRX OM M090 Chapter 8 Control Inspection and Cleaning 8 4 Stop for a Long Time HRS Series 8 10...
Страница 145: ...HRX OM M090 Chapter 9 Documents HRS Series 9 1 Specifications List 9 1 Chapter 9 Documents 9 1 Specifications List...
Страница 162: ...HRX OM M090 Chapter 9 Documents 9 10 Daily Check Sheet HRS Series 9 18...
Страница 165: ......