Chapter 5 Display and setting of various functions
5.16
Alarm customize function
HRS Series
5-36
5.16.2 Alarm customize function setting and checking
The table below explains the setting items of the alarm customize function
and the initial values.
Table 5.16-1
List of set alarm customize function
(
1/2
)
Display
Item
Contents
Initial value
(Default setting)
Changing of
low tank level Set the operation when alarm No. AL01 "Low
tank level" is generated.
A.STP
Changing of circulating
fluid discharge
temperature rise
Set the operation when alarm No. AL03
"circulating fluid discharge temperature rise" is
generated.
A.RUN
Detection temperature for
circulating fluid discharge
temperature rise
Sets the detection temperature for the alarm of
alarm NO. AL03 "circulating fluid discharge
temperature rise ".
Alarm signal is generated when the temperature
becomes higher than this temperature.
45.0
o
C
(113.0
o
F)
Changing of circulating
fluid discharge
temperature drop
Set the operation when alarm No. AL04"
circulating fluid discharge temperature drop “is
generated.
A.RUN
Detection
temperature for
circulating fluid discharge
temperature drop
Sets the detection temperature for the alarm of
alarm NO. AL04 "circulating fluid discharge
temperature drop ".
Alarm signal is generated when the temperature
becomes lower than this temperature.
1.0
o
C
(33.8
o
F)
Changing of circulating
fluid discharge pressure
rise
Set the operation when alarm No. AL08
"circulating fluid discharge pressure rise " is
generated.
A.RUN
Detection pressure for
circulating fluid discharge
pressure rise
Sets the detection pressure for the alarm of alarm
NO. AL08 "circulating fluid discharge pressure
rise ".
Alarm signal is generated when the pressure
becomes higher than this pressure.
0.30MPa
(44PSI)
Changing of circulating
fluid discharge pressure
drop
Set the operation when alarm No. AL09
"circulating fluid discharge pressure drop" is
generated.
A.RUN
Detection
pressure for
circulating fluid discharge
pressure drop
Sets the detection pressure for the alarm of alarm
NO. AL09 "circulating fluid discharge pressure
drop ".
Alarm signal is generated when the pressure
becomes lower than this pressure.
0.05MPa
(7PSI)
Changing of operation
when
communication error
Set the operation when the alarm No. AL19
“Communication error” is generated.
OFF
The monitoring time of
communication error
Set the alarm monitoring time when the alarm No.
AL19 “Communication error” is generated. Alarm
signal is generated when the monitoring time is
exceeded.
30 sec
Changing of contact input
signal 1 detection
Set the operation when the alarm No. AL31
“contact input signal 1 detection” is generated.
A.STP
Changing of contact input
signal 2 detection
Set the operation when the alarm No. AL32
“contact input signal 2 detection” is generated.
A.STP
Changing of
DC line fuse
cut
Set the operation when the alarm No. AL21 “DC
line fuse cut” is generated.
A.STP
Changing of water leakage Set the operation when the alarm No. AL33
“water leakage” is generated.
A.STP
*
1
Changing of electric
resistivityy/conductivity
rise
Set the operation when the alarm No. AL34
“Electric resistivity/conductivity rise” is generated. OFF
*
2
Upper limit of electric
resistivity/conductivity rise
Sets the detection level for the alarm of alarm
NO. AL34 "Electric resistivity/conductivity rise".
Alarm signal is generated when the level
becomes higher than this level.
- - - -
*
2
Содержание Series HRS012-A
Страница 8: ...HRX OM M090 Contents HRS Series...
Страница 144: ...HRX OM M090 Chapter 8 Control Inspection and Cleaning 8 4 Stop for a Long Time HRS Series 8 10...
Страница 145: ...HRX OM M090 Chapter 9 Documents HRS Series 9 1 Specifications List 9 1 Chapter 9 Documents 9 1 Specifications List...
Страница 162: ...HRX OM M090 Chapter 9 Documents 9 10 Daily Check Sheet HRS Series 9 18...
Страница 165: ......