HRX-OM-M090
Chapter 5 Display and setting of various functions
5.19
Communication function
HRS Series
5-64
38.
Select contact input signal 2 from the table below with [
▲
] key or [
▼
] key, and confirm
by pressing “SEL”.
Table 5.19-20
List of set value
Set value
Explanation
Initial value
(Default setting)
Without input signal
○
Input of run/stop signal
External switch signal input(N.O. type)
External switch signal input (N.C. type)
Remote signal
∗
7
∗
7
:
When the setting of the serial protocol is “Simplified communication protocol 2”, “Remote
signal” cannot be set.
Contact input signal 2 type Setting
and checking
39.
Press the [SEL] key once.
The set screen of contact input signal 2 type
is displayed on the digital display.
PV
SV
40.
Select contact input signal 2 type from the table below with [
▲
] key or [
▼
] key, and
confirm by pressing “SEL”.
Table 5.19-21
List of set value
Set value
Explanation
Initial value
(Default setting)
Setting/checking are not available if the
setting of contact input signal 1 is OFF.
Alternate signal
○
Momentary signal
∗
8
∗
8 Can be set when the setting of contact input signal 2 is "Run/Stop signal input" or "Remote signal"
Contact input signal 2 delay timer of reading
Setting
and checking
41.
Press the [SEL] key once.
The set screen of contact input signal 2 delay timer of reading is displayed on the digital
display.
PV
SV
Содержание Series HRS012-A
Страница 8: ...HRX OM M090 Contents HRS Series...
Страница 144: ...HRX OM M090 Chapter 8 Control Inspection and Cleaning 8 4 Stop for a Long Time HRS Series 8 10...
Страница 145: ...HRX OM M090 Chapter 9 Documents HRS Series 9 1 Specifications List 9 1 Chapter 9 Documents 9 1 Specifications List...
Страница 162: ...HRX OM M090 Chapter 9 Documents 9 10 Daily Check Sheet HRS Series 9 18...
Страница 165: ......