HRX-OM-M090
Chapter 4 Starting the Product
HRS Series
4.3
Preparation of circulating fluid
4-5
4.
Press the [RESET] key ([
▼
] and [
▲
] keys simultaneously) to reset the alarm.
The alarm (tank fluid level is low) is reset, and the [ALARM] lamp and [ ] lamp are
turned off. The display returns to the initial screen of the main menu: “Circulating fluid
temp. / Circulating fluid set temp.” Press the [PUMP] key (press [RUN/STOP] key and
[MENU] key simultaneously) to start independent operation of the pump.
Fig. 4-7 Alarm release
5.
Repeat steps 1 to 4 to supply the circulating fluid to the customer’s device and piping.
The tank level must be “H” on the tank liquid level indicator
Press together
OFF
OFF
Be sure to reset the alarm on the operation display panel of the alarm.
Alarm reset
is not accepted from any screen except the alarm display menu. Refer to 5.2.1 Key
operations.