-70-
No.PS
※※
-OMU0012-A
○Power supply/output lead wire
•ZS-31-B
•ZS-31-C
Conductor area
0.15 mm
2
(AWG26)
Insulator
Outside diameter
1.0 mm
Colour
Brown, Blue, Black (3 core)
Sheath
Finished outside diameter
3.4
Страница 1: ...No PS OMU0012 A PRODUCT NAME Sensor Monitor MODEL Series Product Number PSE3 AC...
Страница 2: ...on selection mode 25 Default setting 25 F 0 Units selection function 27 F 1 Setting of OUT1 30 F 2 Setting of OUT2 33 F 3 Digital filter setting 35 F 4 Auto preset function 36 F 6 Fine adjustment of d...
Страница 3: ...equipment failure when configuring the equipment 2 Only personnel with appropriate training should operate machinery and equipment The product specified here may become unsafe if handled incorrectly T...
Страница 4: ...the failure of the product 3 Prior to using SMC products please read and understand the warranty terms and disclaimers noted in the specified catalog for the particular products 2 Vacuum pads are excl...
Страница 5: ...ful fluids Fire malfunction or damage to the product can result Verify the specifications before use Do not operate in an atmosphere containing flammable or explosive gases Fire or an explosion can re...
Страница 6: ...esign and selection installation wiring environment adjustment operation maintenance etc described below must also be followed Product specifications Use the specified voltage Otherwise failure or mal...
Страница 7: ...power or high voltage cables Otherwise the product can malfunction due to interference of noise and surge voltage from power and high voltage cables to the signal line Route the wires piping of the pr...
Страница 8: ...ate close to a heat source or in a location exposed to radiant heat Otherwise malfunction can result Adjustment and Operation Turn the power on after connecting a load Otherwise it can cause excess cu...
Страница 9: ...output lead wire ZS 31 B Straight 5 m ZS 31 C Right angle 5 m Assembly type connector PCA 1557743 Caution The sensor connection lead wire M12 M12 is not provided by SMC It should be prepared by the u...
Страница 10: ...ng condition LCD display Displays the current status of pressure setting mode selected display units and error code 4 types of display can be selected for the main display Single colour of constant re...
Страница 11: ...ctuation of displayed value for sharp start up or fall of the pressure When the function is valid digital filtering is reflected to the ON OFF of the switch output Output chattering or flicker in the...
Страница 12: ...ircuit and the case K Key lock function Function that prevents changes to the settings of the product disables button operation M Manual setting Manual pressure setup without using auto preset This te...
Страница 13: ...esolution Reversed output One of the switch output types In hysteresis mode the switch output is turned ON when pressure less than or equal to the switch output set value is detected In window compara...
Страница 14: ...tion Installation Direct mounting Install the product with M4 screw 2 pcs or equivalent Screws are prepared by the user Refer to the dimensions page 69 for the diameter and depth of the mounting screw...
Страница 15: ...r such as a line noise filter ferrite between the switching power supplies or change the switching power supply to the series power supply Wiring connections Align the body connector key and the cable...
Страница 16: ...uts Pressure sensor 3 wire type Max 20 mA Residual voltage 1 V or less Setting of NPN open collector 2 outputs Pressure sensor 2 wire type Max 30 V 20 mA Residual voltage 1 V or less Setting of PNP op...
Страница 17: ...e turned on When the pressure falls below the set value by the amount of hysteresis or more the switch will be turned off The default setting is that the output is turned ON at 0 5 MPa when the pressu...
Страница 18: ...y by setting the F10 sub display setting If the sub display is switched during the arbitrary display setting the display will be returned to the arbitrary display 30 seconds later The default setting...
Страница 19: ...ge setting Pressure range setting Press the or button to select pressure range Additional range minimum unit setting Press or button to select the minimum unit Press the button to set Other than USEr...
Страница 20: ...e that is required to be displayed when the sensor input signal is 100 The setting range is 1500 to 1500 digit Press the button to set Move on to display unit setting Display unit setting Press the or...
Страница 21: ...or button to select switch output specification Press the button to set Return to function selection mode F 0 Setting of the switching function of the pressure range display unit and switch output spe...
Страница 22: ...y 1 Press the button once when the item to be changed is displayed on the sub display The set value on the sub display right will start flashing 2 Press the or button to change the set value The set v...
Страница 23: ...on and WH1 WH2 hysteresis following the instructions given on page 21 When reversed output is selected the sub display left shows n1L n2L and n1H n2H Please refer to the List of output modes on page 3...
Страница 24: ...ge 55 3 Change the set value with or button and press the button to set the value Then the setting moves to the delay time of the switch output The snap shot function can be used Refer to page 55 4 Pr...
Страница 25: ...he upper limit of the switch operation WH1 WH2 hysteresis and dt1 dt2 delay time following the instructions given on page 23 When reversed output is selected the sub display left shows n1L n2L and n1H...
Страница 26: ...0 Pressure range display unit and switch output specifications Page 27 Item Default setting Connected sensor range 1 MPa Display units Units specification Nil or M MPa Units specification P psi Switch...
Страница 27: ...witch output can be selected 1 0 ms or less Display colour Select the display colour Output ON Green Output OFF Red Linked to OUT Other parameter settings Item Page Default setting F 3 Digital filter...
Страница 28: ...e setting Input value setting Available display unit and minimum set value Pressure range Rated pressure Display MPa kPa Pa Kgf cm2 bar mbar psi inHg mmHg mmH2O Fine differential pressure 2 kPa 0 002...
Страница 29: ...lue Set the value that is required to be displayed when the sensor input signal is 0 The setting range is 1500 to 1500 digit Press the button to set Other than USEr is selected Press the button to mov...
Страница 30: ...fferent depending on the pressure range Refer to page 27 kPa MPa Pa can still be selected if the product does not have the units selection function Press the button to set Switching setting of switch...
Страница 31: ...on Move on to output mode setting Press the button to set Move on to reversed output setting Press the button to set Move on to pressure setting Pressure setting Set the pressure based on the setting...
Страница 32: ...lay time referring to the setting method on page 23 Press the button to set Move on to display colour setting Press the button to set Return to function selection mode F 1 Setting of OUT1 completed 1...
Страница 33: ...point at which the switch output changes is outside of the set pressure range due to the selection of normal or reversed output the hysteresis value is automatically adjusted The figure above shows an...
Страница 34: ...put mode setting Press the or button to select the required output mode Press the button to set Move on to reversed output setting Reversed output setting Press the or button to select the reversed ou...
Страница 35: ...lay time referring to the setting method on page 23 Press the button to set Move on to display colour setting Display colour setting Press the or button to select the display colour Press the button t...
Страница 36: ...ction selection mode to display F 3 Press the button Move on to digital filter setting Press the button to set Return to function selection mode F 3 Digital filter setting completed 1 Each set value i...
Страница 37: ...ction selection mode to display F 4 Press the button Move on to Auto preset function Press the button to set Return to function selection mode F 4 Auto preset function completed Press the button in me...
Страница 38: ...d measurement will be stopped and 4 Selection of auto preset OUT2 mode will return 4 Selection of auto preset OUT2 mode Press the button in measurement mode to display AP2 REdY If setting of OUT2 is n...
Страница 39: ...ess the or button in function selection mode to display F 6 Press the button Move on to fine adjustment of display value Fine adjustment of display value Press the or button to change adjustment rate...
Страница 40: ...r the sub display Sub display left setting Set the sub display left from the selection list on page 41 Press the button to set Move to sub display right setting Sub display right setting Set the sub d...
Страница 41: ...tion displays the items and values on the sub display The displayed item varies depending on the setting of the output mode Select the displayed items by pressing the or button in measurement mode Hys...
Страница 42: ...When window comparator mode is selected OUT1 window comparator mode When window comparator mode is selected Set value for OUT2 hysteresis mode When hysteresis mode is selected OUT2 hysteresis mode Whe...
Страница 43: ...rror output Normal Reversed output Switch output off When using the 2 value display function 3 step setting is not available for the display When setting 3 step select each set value to be displayed b...
Страница 44: ...The threshold bar will not be displayed Only the pressure value meter is displayed Output mode Output style Threshold bar display style Hysteresis mode Normal output Reversed output Window comparator...
Страница 45: ...to the table below Rated range Display at atmospheric pressure Other than compound pressure or Compound pressure or Character string display The Character string display function will display the spec...
Страница 46: ...ay resolution Press the button to set Return to function selection mode F11 Display resolution setting completed The display resolution is not possible to be selected while setting the additional rang...
Страница 47: ...ving mode Power saving mode Press the or button to select the power saving mode Press the button to set Return to function selection mode F80 Power saving mode completed In power saving mode when butt...
Страница 48: ...checking Press the or button to input the security code on the sub display right The default setting is 000 For instructions on how to enter the security code refer to How to input and change the secu...
Страница 49: ...pressing the button for 1 second At this point the changing of the security code is not completed Return to the change of setting again by pressing the or button Press the button for 1 second to set R...
Страница 50: ...igit flashes when the button is pressed at the least significant digit The order of displayed characters is A b Y Z 0 1 9 symbol space Characters which can be displayed are different for 1 digit on th...
Страница 51: ...f functions Return to oFF not used then press the button to set Return to function selection mode F90 Setting of all functions completed Setting of each function Every time the button is pressed the d...
Страница 52: ...10 Output mode setting of OUT2 11 Reversed output setting of OUT2 12 Pressure setting of OUT2 13 Hysteresis setting of OUT2 14 Delay time setting of OUT2 15 Display colour setting 16 Digital filter se...
Страница 53: ...n function selection mode to display F98 Press the button Move on to output check Output check Press the or button to select output check n Normal output is selected Press the button to set Return to...
Страница 54: ...o select OUT2 output check Press the button to return to n normal output then press the button to set Return to function selection mode F98 Output check completed Measurement mode can return from any...
Страница 55: ...y F99 Press the button Move on to reset to default settings Reset to default settings Press the or button to display ON then press the and buttons simultaneously for 5 second or longer oFF not use is...
Страница 56: ...ess Err is displayed on the sub display right and the set value is not changed Afterwards it is possible to adjust the value by pressing the or button Peak bottom value indication The maximum minimum...
Страница 57: ...roximately 1 second Each setting and peak bottom values are displayed with and buttons Operation Without security code input 1 Press the button for 5 seconds or longer in measurement mode When oPE is...
Страница 58: ...g LoC or UnL will be displayed on the sub display 2 Select the un locking UnL with or button Setting is recognized by pressing the button then security code is required 3 For instructions on how to en...
Страница 59: ...s the button to make the next digit to the right flash If the button is pressed at the last digit the first digit will start flashing After the setting is complete Press and hold the button for 1 seco...
Страница 60: ...on The current setting LoC or UnL will be displayed on the sub display Press the and buttons simultaneously for 5 second or longer Press the and buttons simultaneously for 5 second or longer Display i...
Страница 61: ...t installation etc Please consult SMC Yes No The sensor monitor does not operate normally Refer to Trouble No 1 The switch output does not turn OFF The operation light is ON The switch output generate...
Страница 62: ...ect Refer to Trouble No 9 Refer to Trouble No 9 Refer to Trouble No 11 The display is missing Refer to Trouble No 10 The display accuracy does not meet the specifications Refer to Trouble No 12 The di...
Страница 63: ...Check the SW output specification setting Check if the SW output is PNP while NPN is intended to be set and vice versa Set the SW output specification again Lead wire broken Check if there is bending...
Страница 64: ...er limit HHH 1 Check if the pressure exceeds the upper limit of the set pressure range 2 Check if foreign matter has entered the piping 1 Reset applied pressure to a level within the set pressure rang...
Страница 65: ...part of the lead wire 1 Check and correct the wiring 2 Correct the wiring bend radius and stress 11 Pressure display is unstable when products are in close proximity to each other Variation within th...
Страница 66: ...not work Key lock mode is activated Check if the key lock function is turned on Check the key lock function Product failure Replace the product 15 The operation is unstable chattering Effect of line...
Страница 67: ...ment mode automatically 1 second later The zero clear range varies by 1 F S due to variation between individual products Release the applied pressure to atmospheric pressure and retry the zero clear o...
Страница 68: ...Input impedance 51 M Number of inputs 1 input Connection method M12 4 pin connector Protection Over voltage protection up to a voltage of 26 4 V Display Unit 3 Select from MPa kPa Pa kgf cm2 bar mbar...
Страница 69: ...SE531 PSE541 PSE561 0 to 101 kPa 10 to 105 kPa 0 1 kPa PSE533 PSE543 PSE563 PSE573 100 to 100 kPa 105 to 105 kPa 0 1 kPa PSE532 0 to 100 kPa 10 to 105 kPa 0 1 kPa PSE564 PSE574 0 to 500 kPa 50 to 525...
Страница 70: ...69 No PS OMU0012 A Dimensions...
Страница 71: ...70 No PS OMU0012 A Power supply output lead wire ZS 31 B ZS 31 C Conductor area 0 15 mm2 AWG26 Insulator Outside diameter 1 0 mm Colour Brown Blue Black 3 core Sheath Finished outside diameter 3 4...
Страница 72: ...018 4 14 1 Sotokanda Chiyoda ku Tokyo 101 0021 JAPAN Tel 81 3 5207 8249 Fax 81 3 5298 5362 URL http www smcworld com Note Specifications are subject to change without prior notice and any obligation o...