-23-
No.PS
※※
-OMU0012-A
Simple Setting Mode
<Operation>
[Simple setting mode (hysteresis mode)
In the simple setting mode, the set value, hysteresis and delay time can be changed while checking the
current pressure value (main display).
(1) Press and hold the
button between 1 and 3 seconds in measurement mode. [SEt] is displayed on
the main display. When the button is released while in the [SEt] display, the current pressure value is
displayed on the main display, [P_1] or [n_1] is displayed on the sub display (left), and the set value is
displayed on the sub display (right) (Flashing).
(2) Change the set value with
or
button, and press the
button to set the value. Then, the
setting moves to hysteresis setting. (The snap shot function can be used. (Refer to page
))
(3) Change the set value with
or
button, and press the
button to set the value. Then, the
setting moves to the delay time of the switch output.
(The snap shot function can be used. (Refer to page
(4) Press the
or
button, the delay time of the switch output can be selected.
Delay time setting can prevent the output from chattering.
(5) Press the
button for 2 seconds or longer to complete the OUT1 setting.
[P_2] or [n_2] is displayed on the sub screen (left). Continue with setting the OUT2.
Press and hold the
button for 2 seconds or longer to complete the setting. The product will return
to measurement mode.
1: Selected items (1) to (4) become valid after pressing the
button.
2: After enabling the setting by pressing the
button, it is possible to return to measurement mode by pressing the
button for 2 seconds or longer.
3: When the output mode (refer to page
) is set to error output or switch output OFF, the simple setting mode cannot be used.