Function Selection Mode
■
Function selection mode
In measurement mode, press the
button between 3 and 5 seconds, to display [F 0]. Select to display
the function to be changed [F
□□]. Press and hold the
button for 2 seconds or longer in function
selection mode to return to measurement mode.
: Some products do not have all the functions. If no function is available or selected due to configuration of other functions, [- - -] is
displayed on the sub display (right).
■
Default setting
The default setting is as follows.
If no problem is caused by this setting, keep these settings.
To change a setting, enter function selection mode.
•
Switching function of [F 0] Pressure range, display unit and switch output specifications
Item
Default setting
Connected sensor range
1 MPa
Display units
Units specification ["Nil" or M]: [MPa]
Units specification [P]: psi
Switch output specifications
NPN
•
[F 1] Setting of OUT1
Item
Explanation
Default setting
Output mode
Either hysteresis mode, window comparator mode, error output
or switch output OFF can be selected.
Hysteresis mode
Reversed output
Selects which type of switch output is used, normal or reversed.
Normal output
Pressure setting
Sets the ON and OFF point of the switch output.
0.500 MPa
Hysteresis
Appropriate setting of the hysteresis will prevent the switch
output from chattering.
0.050 MPa
Delay time
Delay time of the switch output can be selected.
1.0 ms or less
Display colour
Select the display colour.
Output ON : Green
Output OFF: Red
(Linked to OUT)