-33-
No.PS
※※
-OMU0012-A
■
[F 2] Setting of OUT2
Set the output mode of OUT2.
Output turns on when the pressure is greater than the set value. The default setting is to turn on the product
when the pressure reaches the center of the atmospheric pressure and upper limit of the rated pressure
range.
Please refer to the "List of output modes" on page
for the relationship between the set items and operation.
<Operation>
Press the
or
button in function selection mode to display [F 2].
Press the
button.
Move on to output mode setting.
Output mode setting
Press the
or
button to select the required output mode.
Press the
button to set.
Move on to reversed output setting.
Reversed output setting
Press the
or
button to select the
reversed output.
Press the
button to set.
Move on to pressure setting.
Pressure setting
Set the pressure based on
the setting method on
page
Hysteresis mode: [P_1]
Window comparator mode: [P1L] [P1H]
"P" is changed to "n" as [P_1]
[n_1] when
reversed output is selected.
The snap shot function can be used.
(Refer to page
Press the
button to set.
Move on to hysteresis setting.
[OFF] Switch output
OFF is selected.
Press the
button to move on to
display colour setting.
[Err] Error output is
selected.
Press the
button
to move on to display
colour setting.