-22-
No.PF
※※
-OMS0002-B
Outline of Settings [Measurement mode]
Power is supplied
The output will not operate for 3 seconds after supplying power.
The identification code of the product is displayed.
[Measurement mode]
Measurement mode is the condition where the flow is detected and displayed, and the
switch function is operating.
This is the basic mode; other modes should be selected for set-point changes and other
function settings.
Sub display
In measurement mode, the sub display can be temporarily changed (for 30 seconds) by pressing
the
or
button.
: Example for 500 L/min type
: The set values of OUT2 and the accumulated value of OUT2 cannot be displayed.
: To display other indications than "Set values" normally, perform settings referring to the function selection mode [F10]
).
Press the
button
once.
Press the
button for 2
seconds or
longer.
Flow Setting
[3 step setting mode]
.)
Function Setting
[Function selection mode]
.)
Other Functions
.)
: The outputs will continue to operate during setting.
: If a button operation is not performed for 30 seconds during the setting, the display will flash (This is to prevent the setting from
remaining incomplete if, for instance, an operator were to leave during setting).
: 3 step setting mode and Function selection mode are reflected on each other.