-65-
No.PF
※※
-OMS0002-B
■
Error indication
Error name
Error display
Description
Measures
Instantaneous flow
error
The flow has exceeded the upper limit of
the flow display range.
Reduce the flow.
Fluid is flowing in the reverse direction
by at least -5% of the maximum rated
flow value.
Connect the fluid flow in the
correct direction.
OUT1 over current
error
The switch output (OUT1) load current
has exceeded 80 mA.
Turn the power OFF and
remove the cause of the over
current. Then turn the power
ON again.
OUT2 over current
error
The switch output (OUT2) load current
has exceeded 80 mA.
System error
An internal data error has occurred.
Turn the power OFF and turn
it ON again.
Accumulated flow
error
Accumulated flow
is displayed
(Flashing)
The accumulated flow has exceeded the
accumulated flow range.
(For accumulated increment)
Reset the accumulated flow.
(Press the
and
buttons simultaneously for 1
second or longer) (page
Accumulated flow
is displayed
(Flashing)
The accumulated flow has reached the
set accumulated flow value.
(For accumulated decrement)
: If the error cannot be reset after the above measures are taken, then please contact SMC.