[F31] Orientation correction function
This function can correct a display error of flow caused by the mounting orientation.
If the product is mounted vertically, the displayed flow rate will be seriously affected around a zero flow rate
and when the fluid pressure is high. This function can be used to reduce the display error that occurs when
the product is mounted vertically.
<Operation>
Press the
or
button in function selection mode to display [F31] on the main display.
[PoS] and [the current set value] are displayed in turn on the sub display.
Press the
button.
Orientation
[PoS] is displayed on the main display.
[The current set value] flashes on the sub display.
Press the
or
button to select.
Press the
button to set.
Supply pressure
[PrS] is displayed on the main display.
[The current set value] flashes on the sub display.
Press the
or
button to select.
Press the
button to set.
[F31] Setting of the orientation correction function completed.
Return to function selection mode.