No.DIG-31900-OM002
65
Scale Plate Adjustment
(1) Attention should be taken not to have finger caught between the indicator and scale plate
during position adjustment of the scale plate.
(2) Scale plate edge is sharp. Attention should be taken.
(1) After adjusting the positioner zero/span, mount the scale plate to DA surface (Direct operation)
or RA (Reversed operation) in correct direction (See Fig. 47).
(2) Stop the actuator open degree in the middle (50% of positioner input current), and adjust the
indicator position so that the indicator position match with gauge at 50% (See Fig. 48). If
indicator position does not match with 50% of the gauge even if adjusted, adjust the fork lever
unit angle correctly referring “
■
Initial Adjustment
”
*
1
.
(3) Confirm if the indicator indicate 0% and 100% of the gauge at the start and end of the actuator. If
it does not, loosen the cross recessed socket head screw for mounting to the dial using a
spanner, then slide the scale plate (See Fig. 49, 50).
DA surface
(Direct operation)
RA surface
(Reversed operation)
Needle adjusting screw
Cross recessed hexagon bolt
for scale plate mounting
Fig. 47
Angle becomes 90
°
when
center lines are in line.
S
lid
e
Fig. 50
1: If the fork lever-type fitting angle is
adjusted after calibration, adjust the
span (parameter code: C70).
Caution
!
Fig. 48
Fig. 49
Cross recessed hexagon bolt
for scale plate mounting
Содержание IP8101 Series
Страница 1: ...No DIG 31900 OM002 H SMART POSITIONER ROTARY TYPE PRODUCT NAME IP8101 Series MODEL Series...
Страница 15: ...No DIG 31900 OM002 14 Table 6 Piping Layout...
Страница 75: ...No DIG 31900 OM002 74 Drawing...
Страница 76: ...No DIG 31900 OM002 75...
Страница 77: ...No DIG 31900 OM002 76...
Страница 78: ...No DIG 31900 OM002 77...
Страница 79: ...No DIG 31900 OM002 78...
Страница 80: ...No DIG 31900 OM002 79...
Страница 81: ...No DIG 31900 OM002 80...
Страница 82: ...No DIG 31900 OM002 81...
Страница 83: ...No DIG 31900 OM002 82...
Страница 84: ...No DIG 31900 OM002 83...