No.DIG-31900-OM002
33
(500) Forced fully-close/
fully-open setting
*
6
(600) Dead band setting
Fig. 28
Dead band setting is available. Dead band setting makes the
operation near the target value gentle because the integration
time (I constant) will be cleared, and that makes stability
improved. Dead band can be set in the range between 0.0 and
10.0%. The default value at shipping is 0.0%.
Target value
Dead band (D.B)
0%
S
tr
ok
e
Time
D.B
2
Deviation
The forced fully-closed / fully-open operation can be selected by
setting ON or OFF. The default at shipping is ON. If ON is
selected, the fully-closed setting (510) (input current range
between -0.0 and 10.0%) and the fully-open setting (520) (input
current range between 90.0 to 100.0%) can be set. The default
value at shipping is (510) = 0.5%, and (520) = 99.5%.
95%
(19.2mA)
5%
(4.8mA)
0.5%
100
%
0%
100%
S
tr
ok
e
Input current
(Ex.a) Select (200) = dir when
(510) = 5.0 and (520) = 95.0
0.5%
95%
(19.2mA)
5%
(4.8mA)
100
%
0%
100%
(Ex.b) Select (200) = rvS when
(510) = 5.0, (520) = 95.0
0.5
%
0.5%
S
tr
ok
e
Input current
Fig. 27
The forced fully-close/ fully-open setting will follow the input value
(S value). The position value (P value) will have no influence on
the setting.
6: If forced fully-close/ fully-open is set for a small actuator, it may cause
a very fast actuator movement. In that case, set the forced
fully-close/ fully-open setting at OFF.
Содержание IP8101 Series
Страница 1: ...No DIG 31900 OM002 H SMART POSITIONER ROTARY TYPE PRODUCT NAME IP8101 Series MODEL Series...
Страница 15: ...No DIG 31900 OM002 14 Table 6 Piping Layout...
Страница 75: ...No DIG 31900 OM002 74 Drawing...
Страница 76: ...No DIG 31900 OM002 75...
Страница 77: ...No DIG 31900 OM002 76...
Страница 78: ...No DIG 31900 OM002 77...
Страница 79: ...No DIG 31900 OM002 78...
Страница 80: ...No DIG 31900 OM002 79...
Страница 81: ...No DIG 31900 OM002 80...
Страница 82: ...No DIG 31900 OM002 81...
Страница 83: ...No DIG 31900 OM002 82...
Страница 84: ...No DIG 31900 OM002 83...