No.DIG-31900-OM002
34
(700) Valve opening
characteristics setting
Valve opening characteristic can be selected from the following.
(700) = Lin Linear
Y=X
(710) = EP25 Equal percentage 1:25 (R=25)
Y=(R
X-1
-0.04)×1/0.96
(720) = EP50 Equal percentage 1:50 (R=50)
Y=(R
X-1
-0.02)×1/0.98
(730) = qo25 Quick opening 25:1 (R=25)
Y=(1-R
-X
)×1/0.96
(740) = qo50 Quick opening 50:1 (R=50)
Y=(1-R
-X
)×1/0.98
(750) = USEr
User’s definition
〔
11 polygonal line settings
〕
The default value at shipping is (700) = (Lin) Linear. When u
ser’s
definition (USEr) is set, the following 11 data can be set
*
7
.
However, the setting range is between -20.0 and 120.0%.
(750) Input current 0% position = 0.0% (Default value)
(751)
〃
10% position = 1.0% (
〃
)
(752)
〃
20% position = 4.0% (
〃
)
(753)
〃
30% position = 9.0% (
〃
)
(754)
〃
40% position = 16.0% (
〃
)
(755)
〃
50% position = 25.0% (
〃
)
(756)
〃
60% position = 36.0% (
〃
)
(757)
〃
70% position = 49.0% (
〃
)
(758)
〃
80% position = 64.0% (
〃
)
(759)
〃
90% position = 81.0% (
〃
)
(75A)
〃
100% position = 100.0% (
〃
)
0
100
0
100
100%
Fig. 29
7: Be sure to set all 11 date items.
Linear
Quick opening 50
%
Input current (X)
S
tr
ok
e (Y)
0%
100%
Equal
percentage 50
%
User
Содержание IP8101 Series
Страница 1: ...No DIG 31900 OM002 H SMART POSITIONER ROTARY TYPE PRODUCT NAME IP8101 Series MODEL Series...
Страница 15: ...No DIG 31900 OM002 14 Table 6 Piping Layout...
Страница 75: ...No DIG 31900 OM002 74 Drawing...
Страница 76: ...No DIG 31900 OM002 75...
Страница 77: ...No DIG 31900 OM002 76...
Страница 78: ...No DIG 31900 OM002 77...
Страница 79: ...No DIG 31900 OM002 78...
Страница 80: ...No DIG 31900 OM002 79...
Страница 81: ...No DIG 31900 OM002 80...
Страница 82: ...No DIG 31900 OM002 81...
Страница 83: ...No DIG 31900 OM002 82...
Страница 84: ...No DIG 31900 OM002 83...