No.DIG-31900-OM002
37
(b00) Analog output setting
*
14
“Proportional output (inC)” or “Reversed output (dEC)” can be
selected. When proportional output (inC) is selected, analog
output will increase along with the increase of an actuator’s
stroke. When reversal output (dEC) is selected, analog output will
decrease along with the increase of an actuator’s stroke. The
default value at shipping is (b00) = (inC).
Setting for analog output will follow the position value (P value).
Input value (S value) will have no influence over the setting
*
15
.
14:
Note that once the input current is cut-off, analog output value that
was previously indicated before the cut-off will be maintained.
15: Even if a split range function is utilized, output will be 4 to 20mADC
regardless of
the customer’s applicable range.
0%
100%
4mA
20mA
Cur
ren
t o
utp
ut
Stroke
b00=inC
100%
0%
b00=dEC
Fig. 31
Fig. 30
Upper alarm
(UP)
Set value for alarm
Lower alarm
(Lo)
Set value for alarm
Alarm mode
Alarm output operation
0.5% fixed
0.5% fixed
Position value
100%
Position value
0%
B
Содержание IP8101 Series
Страница 1: ...No DIG 31900 OM002 H SMART POSITIONER ROTARY TYPE PRODUCT NAME IP8101 Series MODEL Series...
Страница 15: ...No DIG 31900 OM002 14 Table 6 Piping Layout...
Страница 75: ...No DIG 31900 OM002 74 Drawing...
Страница 76: ...No DIG 31900 OM002 75...
Страница 77: ...No DIG 31900 OM002 76...
Страница 78: ...No DIG 31900 OM002 77...
Страница 79: ...No DIG 31900 OM002 78...
Страница 80: ...No DIG 31900 OM002 79...
Страница 81: ...No DIG 31900 OM002 80...
Страница 82: ...No DIG 31900 OM002 81...
Страница 83: ...No DIG 31900 OM002 82...
Страница 84: ...No DIG 31900 OM002 83...