No.DIG-31900-OM002
28
Auto Mode Operation
■
Auto Mode
Use an auto mode if controlling an actuator by an input current as a smart positioner.
■
Display Switching Method at Auto Mode
LCD display can be switched as follows according to Fig. 21 with the auto mode
*
1
.
Manual Mode Operation
As it is shown in Fig. 22, the opening of an actuator can be voluntarily controlled by using the
down -button and up-button ( ) in manual mode. While pressing the down -button or
the up -button ( ), the display shows an input value (the target setting value for the actuator).
When the button is released, the display shows the position value of the actuator (actual actuator’s
opening) at that time.
or
or
Input value (%)
Position value (%)
or
Push
or
Release
Up-button: Increases an input value by 1.0% per push
Down-button: Decreases an input value by 1.0% per push
When each button is pressed for a while, an input value is continuously
increased/ decreased by 1.0% for 3sec. After the 3sec., the input value will be
increased/ decreased continuously by 2.0%.
Fig. 22
1: Position value (P value) and input
value’s (S value) indication range
is as follows.
P value : -100 to 200
S value : -50 to 150
Fig. 21
Position value (%)
Indication
flashing
Input value (%)
Deviation
value (%)
▽
button
△
button
▽
button
△
button
△
button
▽
button
Содержание IP8101 Series
Страница 1: ...No DIG 31900 OM002 H SMART POSITIONER ROTARY TYPE PRODUCT NAME IP8101 Series MODEL Series...
Страница 15: ...No DIG 31900 OM002 14 Table 6 Piping Layout...
Страница 75: ...No DIG 31900 OM002 74 Drawing...
Страница 76: ...No DIG 31900 OM002 75...
Страница 77: ...No DIG 31900 OM002 76...
Страница 78: ...No DIG 31900 OM002 77...
Страница 79: ...No DIG 31900 OM002 78...
Страница 80: ...No DIG 31900 OM002 79...
Страница 81: ...No DIG 31900 OM002 80...
Страница 82: ...No DIG 31900 OM002 81...
Страница 83: ...No DIG 31900 OM002 82...
Страница 84: ...No DIG 31900 OM002 83...