IDX-OM-V022
Chapter 10 Specification for Option R
10.3 How to connect the power supply
IDF60/70/80/90 Series
10-2
10.3 How to connect the power supply
Connect the power cables in the following procedure.
1) Remove the front panel.
2) Insert the cable through the strain relief and connect it to the terminal block (refer to the label on the
terminal block).
M3.5 screw tightening torque: 1.0 to 1.3Nm
M4 screw tightening torque: 1.4 to 2.0Nm
During wiring work, do not touch other sections except terminal block.
3) Replace the front panel after wiring is done.
Front panel
GFCI
Strain relief
Power cable entry
test button (gray)
Ground fault display button (white)
Connect to power and ground cable
IDF60-20-R, IDF70-20-R
Terminal connecting screw: M3.5
Crimping terminal width: 8.5mm and below
Applicable electrical wire: 1.25mm
2
or more
IDF80-20-R, IDF90-20-R
Terminal connecting screw: M4.0
Crimping terminal width: 9.5mm and below
Applicable electrical wire: 2.0mm
2
or more
【
Terminal block
】
【
GFCI
】
L N
Terminal block