IDX-OM-V022
Chapter 3 Transportation/Installation
3.2
Installation
IDF60/70/80/90 Series
3-2
3.2 Installation
3.2.1
Location
The product should not be used or stored in the circumstances as follows. Those circumstances will
cause not only malfunction but also failures.
- Locations where the air dryer will be in direct contact with wind and rain. (Locations where relative
humidity is 85% or more.)
- Locations where the product is exposed to water, moisture vapor, salty water, oil and so on.
- Locations where dust or particles are.
- Locations where inflammable or explosive gas are.
- Locations where corrosive gas, solvent, combustible gas are.
- Locations that receive direct sunlight or where radiant heat is generated.
- Locations where ambient temperature is beyond following range:
On-stream: 2 to 45
o
C
Storage: 0 to 50
o
C (when there is no drain water inside of the piping)
- Locations where temperature changes rapidly.
- Locations where strong electromagnetic noise is generated (locations where electromagnetic field,
strong magnetic field, surge is generated)
- Circumstances where static electricity is produced or discharged through the body of the product.
- Locations where strong high frequency wave is generated.
- Locations where danger of thunder is apparent.
- Locations by loading on vehicles, marine vessels, and so on.
- Locations whose altitude is higher than 2,000 meters.
- Circumstances where strong vibration or impact are transmitted.
- Circumstances where too much force and weight are put on the body of the product that causes it to
deform.
- Circumstances where enough spaces cannot be taken to do maintenance (in the plant where the
product is operated).
Spaces needed for maintenance
Front: 600 mm / Rear: 600 mm / Top: 600 mm / Right: 600 mm / Left: 600 mm
- Locations the ventilation grille of the product can be blocked.
- Place where rejection style air of air compressor or other driers (hot wind) is inhaled.
- Place where rapid pressure fluctuation and fluid velocity variation happen.
3.2.2
Anchorage
- The air dryer should be installed on a vibration-free, stable, horizontal flat surface.
- Refer to
“Chapter7 7.3 Dimensions” for the dimensions.
- This model should be installed using anchor bolts (not included) to prevent shifting during a potential
earthquake. (The anchor bolts are available separately as a set.)
Parts No.
Description
Qty.
IDF-AB500
Foundation bolt set
1 set (4 pcs/set)
- Do not use this product with compressed air which contains, or store this product
in an environment which contains the following substance avoid malfunction and
also to avoid injury to the user due to broken parts:
- Corrosive gas, solvents and other harmful chemicals.
WARNING