IDX-OM-V022
Chapter 7 References
IDF60/70/80/90 Series
7.1 Specifications
7-1
Chapter 7 References
7.1 Specifications
Model
Specifications
IDF60-20
IDF70-20
IDF80-20
IDF90-20
O
pe
rati
ng
ran
ge
(Not
e
1
)
Fluid
Compressed Air
Inlet air temperature
o
C
5 to 65
Inlet air pressure
MPa
0.15 to 1.0
(Note8)
Ambient temperature (humidity)
o
C
2 to 45
(Relative humidity 85% or less)
Rate
d
c
on
d
iti
on
s
Air Flow
capacity
m
3
/min
Standard
condition
(ANR)
(Note2)
50Hz
5.3
7.5
10.9
13.5
60Hz
6.1
8.6
12.8
15.5
Compressor
intake
condition
(Note3)
50Hz
5.6
8.0
11.6
14.3
60Hz
6.5
9.1
13.6
16.4
Pressurized Dew Point
o
C
10
Inlet air pressure
MPa
0.7
Inlet air temperature
o
C
35
40
Ambient temperature
o
C
32
Power supply voltage (frequency)
Single-phase 200/200,220V (50/60Hz)
Allowable voltage fluctuation ±10%
(Note4)
Maximum flow capacity
Calculated with correction factor. See page7-2.
E
lec
tr
ic
al
s
pe
c
ifi
c
at
io
ns
Power consumption
(Note5)
50/60Hz
W
770/910
1260/1580
1770/2170
2270/2960
Operating current
(Note5)
50/60Hz
A
4.2/4.6
6.7/7.9
9.7/10.9
11.8/14.8
Applicable circuit breaker capacity
(sensitivity current 30mA)
(Note6)
A
10
15
20
30
Condenser
Air-cooled
Refrigerant
R410A (HFC) GWP
:
2088
(Note7)
Refrigerant charge quantity
g
390±10
530±10
630±10
780±10
Auto drain
Float type
(Normally open minimum operating pressure: 0.1MPa)
Drain connection
mm
12
Port size
R1
R1 1/2
R2
Weight
kg
49
68
95
110
Coating color
Body panel: Urban white1
Base: Urban gray2
Note 1: The operation range does not guarantee the use with rated air flow capacity.
Note 2: Air flow capacity under the standard condition (ANR) [20
℃
, Atmospheric pressure, and
65% Relative humidity]
Note 3: Air flow capacity converted by the compressor intake condition [32
℃
, Atmospheric
pressure, and 75% Relative humidity]
Note 4: Do not use this product with continuous voltage fluctuation.
Note 5: These values are reference values under rated conditions, and are not guaranteed. Do not
use these values for the thermal relay set values etc.