HRX-OM-Q026-B
Chapter 3 Transport and Setting Up
3.3
Installation
HRSH Series
3-8
3.3 Installation
3.3.1 Installation
How to mount the product
1.
Insert the product to the anchor bolts that were previously driven on the horizontal floor.
2.
Fasten the nuts to the anchor bolts.
3.
Make sure that there is no looseness on all the anchor bolts and nuts.
【
One point
】
SMC Foundations bolt set [IDF-AB500] (SUS M10x50mm) is applicable.
Fig. 3-4 Installation procedures
Install the product on the horizontal floor.
Prepare the M10 anchor bolts that are appropriate to the material of
the floor that the product will be installed. Drive the anchor bolts at
least at two places of the left and right side of the product each (totally
four places). Refer to the “8.2 Outline dimensions” for the dimensions
for the position of the anchor bolts.
Floor
Anchor bolt
Nut
Base of the product
Hole for anchor bolt (12mm)
Anchor bracket
Hole for anchor
bolt (12mm)