HRX-OM-Q026-B
Chapter 5 Display and setting of various functions
HRSH Series
5.20
Alarm customizing function
5-51
Table 5.20-6 List of set alarm customizing function(2/3)
Object alarm
Display
Content
Code
Alarm name
Change content
Default
setting
∗
1
AL03
Circulating fluid
discharge temp. rise
Monitoring start timer
AL04
Circulating fluid
discharge temp. drop
Alarm does not
occur during the set
period of time after
starting operation.
Alarm monitoring will
start after the period.
----
(0)
AL03
Circulating fluid
discharge temp. rise
Range over detection
timer
AL04
Circulating fluid
discharge temp. drop
Alarm does not
occur during the set
period of time after
the temperature
goes out of the
threshold.
5
AL10
High compressor
suction temp.
AL11
Low compressor
suction temp.
AL12
Low super heat
temperature
AL13
High compressor
discharge pressure
AL15
Refrigerant circuit
pressure (high
pressure side) drop
AL16
Refrigerant circuit
pressure (low
pressure side) rise
AL17
Refrigerant circuit
pressure (low
pressure side) drop
AL18
Compressor running
failure
AL24
Compressor suction
temp. sensor failure
AL26
Compressor fluid
discharge pressure
sensor failure
AL27
Compressor suction
pressure sensor
failure
AL37
Compressor
discharge temp.
sensor failure
AL38
Compressor
discharge temp. rise
AL43
Fan inverter error
AL44
Fan inverter error
AL45
Compressor inverter
error
Compressor stop alarm
AL46
Compressor inverter
error
Alarm operation
P.RUN
*1: Regarding the detail of the default setting, refer to “Table 5.20-1 to 4 Alarm setting and customizing”.
Содержание HRSH150-A*-20 Series
Страница 7: ...HRX OM Q026 B Contents HRSH Series Chapter 9 Product Warranty 9 1...
Страница 8: ......
Страница 50: ...HRX OM Q026 B Chapter 3 Transport and Setting Up 3 5 Fill of circulating fluid HRSH Series 3 32...
Страница 60: ...HRX OM Q026 B Chapter 4 Starting the Product 4 6 Adjustment of Circulating Fluid flow rate HRSH Series 4 10...
Страница 177: ......