Chapter 5 Display and setting of various functions
5.20
Alarm customizing function
HRSH Series
5-60
Monitoring start timer Setting and Checking
32.
Press the [SEL] key once.
Setting screen of the monitoring start timer is displayed on the digital display.
PV
SV
33.
Select monitoring start timer from the table below with [
▲
] key or [
▼
] key, and confirm
by pressing “SEL”.
Table
5.20-23
List of set value
Set value
Explanation
Initial value
(Default setting)
Setting and checking are impossible when "0:
Continuous monitoring" or "1: Automatic
monitoring" is selected for the setting of AS21
"Temperature alarm monitoring method".
○
to
Sets the time when alarm monitoring starts
Setting unit is 1 minute.
∗
Settings of this function and example of alarm generating timing for 5.15.3 "Setting of
temperature alarm monitoring method and generation timing".
Range over detection timer; Setting and Checking
34.
Press the [SEL] key once.
Setting screen of the range over detection timer is displayed on the digital display.
PV
SV
35.
Select the time of the range over detection timer from the table below with [
▲
] key or
[
▼
] key, and confirm by pressing “SEL”.
Table
5.20-24
List of set value
Set value
Explanation
Initial value
(Default setting)
to
Sets time from detecting the alarm to
generation of the alarm.
Setting unit is 1 second.
∗
Settings of this function and example of alarm generating timing for 5.15.3 "Setting of
temperature alarm monitoring method and generation timing".
Содержание HRSH150-A*-20 Series
Страница 7: ...HRX OM Q026 B Contents HRSH Series Chapter 9 Product Warranty 9 1...
Страница 8: ......
Страница 50: ...HRX OM Q026 B Chapter 3 Transport and Setting Up 3 5 Fill of circulating fluid HRSH Series 3 32...
Страница 60: ...HRX OM Q026 B Chapter 4 Starting the Product 4 6 Adjustment of Circulating Fluid flow rate HRSH Series 4 10...
Страница 177: ......