HRX-OM-Q026-B
Chapter 5 Display and setting of various functions
HRSH Series
5.21
Communication function
5-77
38.
Select contact input signal 2 from the table below with [
▲
] key or [
▼
] key, and confirm
by pressing “SEL”.
Table 5.21-20
List of set value
Set value
Explanation
Initial value
(Default setting)
Without signal input
○
Run/stop signal input
External switch signal input(N.O. type)
External switch signal input (N.C. type)
Remote signal input
∗
7
∗
7
:
When the setting of the serial protocol is “Simplified communication protocol 2”, “Remote
signal” cannot be set.
Contact input signal 2 type Setting
and checking
39.
Press the [SEL] key once.
The set screen of contact input signal 2 type
is displayed on the digital display.
PV
SV
40.
Select contact input signal 2 type from the table below with [
▲
] key or [
▼
] key, and
confirm by pressing “SEL”.
Table 5.21-21
List of set value
Set value
Explanation
Initial value
(Default setting)
Setting/checking are not available if the
setting of contact input signal 1 is OFF.
Alternate signal
○
Momentary signal
∗
8
∗
8 Can be set when the setting of contact input signal 2 is "Run/Stop signal input" or "Remote signal"
Contact input signal 2 delay timer of reading
Setting
and checking
41.
Press the [SEL] key once.
The set screen of contact input signal 2 delay timer of reading
is displayed on the
digital display.
PV
SV
Содержание HRSH150-A*-20 Series
Страница 7: ...HRX OM Q026 B Contents HRSH Series Chapter 9 Product Warranty 9 1...
Страница 8: ......
Страница 50: ...HRX OM Q026 B Chapter 3 Transport and Setting Up 3 5 Fill of circulating fluid HRSH Series 3 32...
Страница 60: ...HRX OM Q026 B Chapter 4 Starting the Product 4 6 Adjustment of Circulating Fluid flow rate HRSH Series 4 10...
Страница 177: ......