5.20.2 Alarm customize function setting and checking
The table below explains the setting items of the alarm customize function
and the initial values.
Table 5.20-5
List of set alarm customizing function(1/2)
Object alarm
Display
Content
Code
Alarm name
Change content
Default
setting
∗
1
Changing of low tank
level
AL01
Low level in tank
Alarm operation
A.STP
Changing of circulating
fluid discharge
temperature rise
Alarm operation
A.RUN
Detection temperature
for circulating fluid
discharge temperature
rise
AL03
High circulating fluid
discharge temp
Alarm threshold
40.0
℃
(104.0
゚
F)
(----)
Changing of circulating
fluid discharge
temperature drop
Alarm operation
A.RUN
Detection temperature
for circulating fluid
discharge temperature
drop
AL04
Circulating fluid
discharge temp. drop
Alarm threshold
1.0
℃
(33.8
゚
F)
(----)
Changing of circulating
fluid discharge
pressure rise
Alarm operation
ASTP
Detection pressure for
circulating fluid
pressure rise
AL08
Circulating fluid
discharge temp. rise
Alarm threshold
1.00MPa
(145PSI)
(----)
Changing of circulating
fluid discharge
pressure drop
Alarm operation
A.STP
Detection pressure for
circulating fluid
discharge
pressure
drop
AL09
Circulating fluid
discharge pressure
drop
Alarm threshold
0.05MPa
(7PSI)
(----)
Changing of
communication error
Alarm operation
OFF
Monitoring time of
communication error
AL19
Communication error
Alarm threshold
----
(30)
Changing of contact
input 1 signal detection
AL31
Contact input 1 signal
detection
Alarm operation
A.STP
Changing of contact
input 2 signal detection
AL32
Contact input 2 signal
detection
Alarm threshold
A.STP
Changing of DC line
fuse cut
AL21
DC line fuse cut
Alarm operation
A.STP
AL03
Circulating fluid
discharge temp. rise
Temperature alarm
monitoring method
AL04
Circulating fluid
discharge temp. drop
Selection of
monitoring method
0
*1: Regarding the detail of the default setting, refer to “Table 5.20-1 Alarm setting and customizing
(1/4)~(4/4)”.
Содержание HRSH150-A*-20 Series
Страница 7: ...HRX OM Q026 B Contents HRSH Series Chapter 9 Product Warranty 9 1...
Страница 8: ......
Страница 50: ...HRX OM Q026 B Chapter 3 Transport and Setting Up 3 5 Fill of circulating fluid HRSH Series 3 32...
Страница 60: ...HRX OM Q026 B Chapter 4 Starting the Product 4 6 Adjustment of Circulating Fluid flow rate HRSH Series 4 10...
Страница 177: ......