Chapter 6 Alarm indication and trouble shooting
HRSE Series
6.1
Alarm Display
6-1
Chapter 6 Alarm indication and trouble
shooting
6.1 Alarm Display
When any alarm occurs, the product responds with the following conditions.
The [ALARM] lamp will flash.
The alarm buzzer sounds.
The alarm no. is displayed on PV.
The thermo-chiller has two types of operation depending on the alarm
status.
One alarm type will stop operation when an alarm is generated during
operation. The other type will not stop operation even when an alarm is
generated.
Re
fer to the “ Table 6-1 Alarm coce list and Troubleshooting ”. When the
operation is forced to stop, the product cannot restart until the alarm is
reset.
When multiple alarms are generated, the alarms are displayed one by
one by pressing the [SEL] key
Alarm with no.1 on the digital display SV is the latest alarm. The alarm
with the highest number is the alarm that was generated first.
【
Example of display
】
The temperature rises gradually, and alarms are
generated in the order AL03, AL02.
The alarm code displayed on the operation panel
is AL02. AL03 are displayed by pressing the [SEL]
key.
Digital display SV displays “2” when AL03 is
displayed.In this example. AL03 is the highest
number. This means AL03 is the alarm generated
first.
Alarm
buzzer
Flash
PV
SV
PV
SV
SEL
SEL