HRX-OM-R039
Chapter 3 Transport and Setting Up
HRSE Series
3.2
Installation
3-3
3.2 Installation
3.2.1
Environment
The product must not be operated, installed, stored or transported in the
following conditions. Potential malfunction or damage to the product may
occur if these instructions are disregarded.
The product does not conform to any Clean room specifications. The pump
and ventilating fan inside the product generate particles.
Location that is outside.
Location that is exposed to water, water vapour, steam, salt water or oil.
Location that is exposed to dust or powder material.
Location that is exposed to corrosive gas, organic solvent, chemical
solution, or flammable gas (the product is not flame-proof)
Location where the ambient temperature is out of the following range:
In transportation and In storage 0 to 50°C
(with no water or circulating fluid in piping)
In operation *Power supply 100V : 5 to 35°C
*Power supply 200/230V : 5 to 40°C
Location where the ambient humidity is out of the following range or where
condensation occurs:
In transportation and storage 15 to 85%
In operation 30 to 70%
Location that is exposed to direct sunlight or heat radiation.
Location that is near heat sources and poor in ventilation.
Location that is subjected to abrupt changes in temperature.
Location that is subjected to strong electromagnetic noise (intense electric
field, intense magnetic field, or surges).
Location that is subjected to static electricity, or conditions where static
electricity can discharge to the product.
Keep the product horizontal to a rigid and flat floor which can
resist the weight of the product, and take measures to prevent the
product from tipping over. Improper installation may cause water
leakage, tipping, damage of the product or injure the operator.
Keep the ambient temperature of the product between 5 to 35
o
C.
Operation below 5
o
C may cause the compressor failure, and
operation above 35
o
C may cause the product to overheat and shut
down.
Power supply 200V : The operating ambient temperature is 5 to
40
o
C.
Do not set up the product in places possibly exposed to leakage of
flammable gas. Should any flammable gas stay around the
product, the product may cause a fire.
Do not use the product outdoors. If the product subjected to rain
or water splash it may cause electrical shock, fire or failure.