HRX-OM-R039
Chapter 5 Display and setting of various functions
5.6
Alarm customize function
HRSE Series
5-14
Table 5.6-2
List of set alarm customize function(2/2)
Display
Item
Contents
Initial value
(Default setting)
Monitoring start timer
Alarm will not be generated during the set period
of time after starting operation. Alarm monitoring
starts when it reaches the set time.
----
Range over
Detection timer
After starting the alarm monitoring, the alarm will
not be generated right away and will be kept not
generated for the set period of time for AL04
"Detection temp for the circulating fluid discharge
temp. increase" and AL06 "Detection temp. for
circulating fluid discharge temp. drop", when the
temperatures goes out of the set range.
5
1.
Press and hold the [MENU] key for approx. 2 sec.
Repeat pressing the key until the setting screen for alarm buzzer sound [
]
appears on the digital display.
PV
SV
PV
SV
PV
SV
PV
SV
2.
Press the [SEL] key once.
"AS02" is displayed, but this feature is not available on this product.
PV
SV
Changing of circulating fluid discharge temperature rise
Setting and checking
3.
Press the [SEL] key once.
The set screen of changing of circulating fluid discharge temperature rise is displayed on
the digital display.
PV
SV
4.
Select
changing of circulating fluid discharge temperature rise from the table below with
[
▲] key or [▼] key, and confirm by pressing “SEL”.
Table 5.6-3
List of set value
Set value
Explanation
Initial value
(Default setting)
This alarm signal is not detected.
Operation continues when this alarm signal is
generated.
✓
Operation is stopped when this alarm signal is
generated.
[