HRX-OM-R039
Chapter 5 Display and setting of various functions
HRSE Series
5.6
Alarm customize function
5-15
Detection temperature for circulating fluid discharge temperature rise
Setting and checking
5.
Press the [SEL] key once.
The set screen of detection temperature for circulating fluid discharge temperature rise is
displayed on the digital display.
PV
SV
6.
Select detection temperature for circulating fluid discharge temperature rise from the
table below with [
▲] key or [▼] key, and confirm by pressing “SEL”.
Table 5.6-4
List of set value
Set value
Explanation
Initial value
(Default setting)
Setting/checking are not available if the setting of the
circulating fluid discharge temperature rise is OFF.
Centigrade
to
Sets detection temp for the circulating fluid discharge
temperature rise.
Temperature unit is Centigrade : Setting unit is 1
o
C
Changing of circulating fluid discharge temperature drop
setting and checking
7.
Press the [SEL] key once.
The set screen of changing of circulating fluid discharge temperature drop is displayed
on the digital display.
PV
SV
8.
Select changing of circulating fluid discharge temperature drop from the table below with
[
▲] key or [▼] key, and confirm by pressing “SEL”.
Table 5.6-5
List of set value
Set value
Explanation
Initial value
(Default setting)
This alarm signal is not detected.
Operation continues when this alarm signal is
generated.
✓
Operation is stopped when this alarm signal is
generated.
Detection
temperature for circulating fluid discharge temperature drop Setting and checking
9.
Press the [SEL] key once.
The set screen of detection
temperature for circulating fluid discharge temperature drop
is displayed on the digital display.
PV
SV