HRX-OM-R039
Chapter 5 Display and setting of various functions
HRSE Series
5.6
Alarm customize function
5-19
26.
Select temperature alarm monitoring method from the table below with [
▲] key or [▼]
key, and confirm by pressing “SEL”.
Table
5.6-7
List of set value
Set value
Item
Explanation
Initial value
(Default setting)
Continuous
monitoring
Alarm monitoring starts at the same
time as it is turned ON.
✓
Automatic
monitoring
When
the
circulating
fluid
temperature is outside of the alarm
threshold range at the time of
operation start, the alarm will not be
generated until the temperature
comes inside the alarm threshold
range.
Monitoring start
timer
Alarm will not be generated until it
reaches the time set for the AS.22
"Monitoring start timer" after the
operation starts.
Alarm monitoring starts when it
reaches the set time.
Automatic
monitoring
+
Monitoring start
timer
Alarm will not be generated until it
reaches the time set for the AS.22
"Monitoring start timer" after the
operation starts.
Alarm monitoring starts when it
reaches the set time.
When
the
circulating
fluid
temperature
enters
the
alarm
threshold range before it reaches
the set time, the alarm monitoring
will be started at that time.
Settings of this function and example of alarm generating timing for 5.6.3 "Setting of temperature alarm
monitoring method and generation timing".
Monitoring start timer Setting and Checking
27.
Press the [SEL] key once.
Setting screen of the monitoring start timer is displayed on the digital display.
PV
SV
28.
Select monitoring start timer from the table below with [
▲] key or [▼] key, and confirm
by pressing “SEL”.
Table 5.6-8
List of set value
Set value
Explanation
Initial value
(Default setting)
Setting and checking are impossible when "0:
Continuous monitoring" or "1: Automatic
monitoring" is selected for the setting of AS21
"Temperature alarm monitoring method".
✓